MachineryFix

INVT AC drive (VFD) · fault code

Goodrive20 (GD20) OL2: VFD overload

OL2 on the INVT Goodrive20 (GD20) is the “VFD overload” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.

Code
OL2
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Drive overload

01 / Causes

What causes OL2

  • Acceleration too fast.
  • Restarting a motor that is still turning.
  • The supply voltage is too low.
  • The load is too heavy.
  • The motor is too large for the VFD.

02 / Checks

What to check for OL2

In the order INVT gives them.

  1. 01Lengthen the acceleration time.
  2. 02Avoid restarting straight after stopping.
  3. 03Check the supply line's power.
  4. 04Choose a VFD with a higher power rating.
  5. 05Choose a suitable motor.

Also in the manual

  • Over communication this fault reads as type 12.

03 / Clearing it

How to clear OL2

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If OL2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overload faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Record the running current and compare it with the drive's rated current.
  2. 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
  3. 03Check acceleration time and boost settings; long periods at high torque add up quickly.

05 / Repair

When OL2 means a repair

If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.

If OL2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Drive overload: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F5 Inverter I2t · A505 Inverter I2t
Siemens SINAMICS G120F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t
Siemens SINAMICS V90F30005 Power unit: Overload I2t
Siemens MICROMASTER 440F0005 Inverter I2T · A0505 Inverter I2T
Allen-Bradley PowerFlex 525F064 Drive Overload
Delta VFD-EoL Overload
Delta C2000oL Over load · oL3 Overload protection at low frequency
Hitachi WJ200E38 Low-speed overload protection
Yaskawa V1000oL2 Drive Overload
Yaskawa A1000oL2 Drive Overload
Yaskawa GA500oL2 Drive Overload
Siemens MICROMASTER 420F0005 Inverter I2t · A0505 Inverter I2t
Siemens MICROMASTER 430F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle
Siemens SINAMICS G110F0005 Inverter I2t · A0505 Inverter I2t
INVT Goodrive200A (GD200A)OL2 VFD overload
Mitsubishi Electric FR-D700E.THT Inverter overload trip (electronic thermal O/L relay function)
Danfoss VLT Micro Drive FC 51Alarm 9 Inverter overloaded

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OL2 won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.