OBF on the Schneider Electric Altivar ATV320 is the “DC bus overvoltage error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.
- Code
- OBF
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- DC bus overvoltage
01 / Causes
What causes OBF
- Braking too sudden, or an overhauling (driving) load.
- The supply voltage is too high.
02 / Checks
What to check for OBF
In the order Schneider Electric gives them.
- 01Lengthen the deceleration time.
- 02Fit a braking resistor if needed.
- 03Turn on deceleration ramp adaptation (BRA), if the application allows it.
- 04Check the supply voltage.
Also in the manual
- Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.
03 / Clearing it
How to clear OBF
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If OBF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus overvoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
- 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
- 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
- 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.
05 / Repair
When OBF means a repair
If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.
If OBF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
DC bus overvoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active |
| Siemens SINAMICS G120 | F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage |
| Siemens SINAMICS V90 | F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage |
| Siemens MICROMASTER 440 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Allen-Bradley PowerFlex 525 | F005 OverVoltage |
| ABB ACS355 | F0002 DC OVERVOLT · A2002 OVERVOLTAGE |
| Delta VFD-E | ov Over-voltage |
| Delta C2000 | ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop |
| Delta ASDA-B2 | AL002 Over voltage |
| Hitachi WJ200 | E07 Over-voltage protection · E15 Input over-voltage |
| INVT Goodrive20 (GD20) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Yaskawa V1000 | ov Overvoltage |
| Yaskawa A1000 | ov Overvoltage |
| Yaskawa GA500 | ov Overvoltage |
| Siemens MICROMASTER 420 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens MICROMASTER 430 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens SINAMICS G110 | F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active |
| INVT Goodrive200A (GD200A) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Mitsubishi Electric FR-D700 | E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage) |
| Danfoss VLT Micro Drive FC 51 | Alarm 7 DC overvoltage |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.