A0912 on the Siemens MICROMASTER 440 is the “Vdc-min controller active” alarm. An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- A0912
- Type
- Alarm (warning)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes A0912
- The DC link voltage (r0026) fell below its minimum, so the Vdc_min controller is using the motor's kinetic energy to support it, which slows the drive. Brief supply failures then do not automatically cause an undervoltage trip.
02 / Checks
What to check for A0912
In the order Siemens gives them.
The manual gives no specific remedy for A0912. Work through the general method for dc bus undervoltage faults below.
03 / Clearing it
How to clear A0912
An alarm is a warning the inverter shows while it keeps running; some alarms reduce the output or pulse frequency to protect the inverter.
If A0912 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When A0912 means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If A0912 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| ABB ACS355 | F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta C2000 | LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error |
| Delta ASDA-B2 | AL003 Under voltage |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa V1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 420 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other MICROMASTER 440 codes
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007