Siemens AC drive (VFD) · fault code

SINAMICS G120 F13100: Know-how protection: Copy protection error

F13100 on the Siemens SINAMICS G120 is the “Know-how protection: Copy protection error” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.

The drive could not read or write its stored parameters, or found them invalid. The drive may start with wrong settings, or refuse to start.

Code
F13100
Type
Fault (stops the drive)
Drive
Siemens SINAMICS G120, CU240B-2, CU240E-2
Kind of fault
Parameter memory

01 / Causes

What causes F13100

  • Know-how protection and copy protection for the memory card are active, and checking the memory card failed.

02 / Checks

What to check for F13100

In the order Siemens gives them.

  1. 01Insert a suitable memory card and switch the inverter's supply off and on again (POWER ON).
  2. 02Or deactivate the copy protection (p7765).

03 / Clearing it

How to clear F13100

  • Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
  • Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
  • Alarms need no acknowledgement: they disappear once the cause is removed.

Clear it once. If F13100 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How parameter memory faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Power-cycle the drive and see whether the fault clears.
  2. 02If it returns, restore the parameters from a backup, or reset to factory settings and set the drive up again.
  3. 03Keep a parameter backup of every drive, so this never means guessing the settings.

05 / Repair

When F13100 means a repair

A memory fault that survives a factory reset needs the control board repaired or replaced.

If F13100 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Parameter memory: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F51 Parameter EEPROM fault · F61 SD card parameter cloning failed · F62 Parameter cloning contents invalid · F63 Parameter cloning contents incompatible · F64 Inverter attempted to do an automatic clone during startup · F395 Acceptance test/confirmation pending
Siemens SINAMICS V90A1019 Writing to the removable data medium unsuccessful · A1032 All parameters must be saved · A1045 Configuring data invalid · A52900 Failure during data copying
Siemens MICROMASTER 440F0051 Parameter EEPROM fault
Allen-Bradley PowerFlex 525F048 Params Defaulted · F100 Parameter Chksum · F101 External Storage
ABB ACS355A5010 Corrupted panel parameter backup file · A5018 Parameter default value is not found · A5025 Software is being uploaded or downloaded · A5029 Memory is not ready · A5040 Parameter download error: the selected set is not in the backup file · A5041 Parameter backup file does not fit into memory
Delta VFD-EcF1.0 Power board CPU write failure · cF1.1 Control board CPU write failure · cF2.0 Power board CPU read failure · cF2.1 Control board CPU read failure
Delta C2000cF1 EEPROM write error · cF2 EEPROM read error
Delta ASDA-B2AL017 Abnormal EEPROM · AL099 DSP firmware upgrade
Hitachi WJ200E08 EEPROM error
Schneider Electric Altivar ATV320EEF1 EEprom control error · EEF2 EEprom power error
INVT Goodrive20 (GD20)EEP EEPROM operation fault
Yaskawa V1000CPF06 EEPROM Data Error · Err EEPROM Write Error
Yaskawa A1000CPF06 EEPROM Memory Data Error · dWF1 EEPROM Memory DriveWorksEZ Data Error · Err EEPROM Write Error
Yaskawa GA500CPF06 Control Circuit Error (EEPROM memory Data Error) · dWF1 EEPROM Memory DWEZ Data Error · Err EEPROM Write Error · LoG Log Com Error
Siemens MICROMASTER 420F0051 Parameter EEPROM fault
Siemens MICROMASTER 430F0051 Parameter EEPROM fault · F0053 I/O EEPROM fault
Siemens SINAMICS G110F0051 Parameter EEPROM fault · F0055 BOP-EEPROM fault
INVT Goodrive200A (GD200A)EEP EEPROM operation fault
Mitsubishi Electric FR-D700E.PE Parameter storage device fault (control circuit board)
Danfoss VLT Micro Drive FC 51Error 86 Copy fail · Error 87 LCP data invalid · Error 88 LCP data not compatible

07 / More codes

Other SINAMICS G120 codes

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F13100 won't clear? Get a technician who knows the SINAMICS G120.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.