AL017 on the Delta ASDA-B2 is the “Abnormal EEPROM” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.
The drive could not read or write its stored parameters, or found them invalid. The drive may start with wrong settings, or refuse to start.
- Code
- AL017
- Type
- Alarm (stops the drive)
- Drive
- Delta ASDA-B2
- Kind of fault
- Parameter memory
01 / Causes
What causes AL017
- The DSP had an error accessing the EEPROM.
- An abnormal hidden parameter.
- The data in ROM is damaged.
02 / Checks
What to check for AL017
In the order Delta Electronics gives them.
- 01Press SHIFT on the panel. An E code of the form EXGAB names the parameter: G is the parameter group and AB its number in hexadecimal, so E320A is P2-10 and E3610 is P6-16. If the alarm appears at power-on, that parameter is out of its reasonable range: correct it and power on again. If it appears during operation, writing the parameter failed: clear it with DI.ARST.
- 02If SHIFT shows E100X, the alarm came from a parameter reset and the drive type is set wrongly: set the correct drive type.
- 03If SHIFT shows E0001 when the servo is switched on, the ROM data is damaged or missing: Delta's instruction is to send the drive back to the distributor or contact Delta.
Also in the manual
- ALM output; servo off. After this alarm a parameter reset is needed before switching the servo on again; if it happens during operation, DI.ARST clears it.
03 / Clearing it
How to clear AL017
- Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
- Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
- AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
- AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.
Clear it once. If AL017 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How parameter memory faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and see whether the fault clears.
- 02If it returns, restore the parameters from a backup, or reset to factory settings and set the drive up again.
- 03Keep a parameter backup of every drive, so this never means guessing the settings.
05 / Repair
When AL017 means a repair
A memory fault that survives a factory reset needs the control board repaired or replaced.
If AL017 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Parameter memory: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F51 Parameter EEPROM fault · F61 SD card parameter cloning failed · F62 Parameter cloning contents invalid · F63 Parameter cloning contents incompatible · F64 Inverter attempted to do an automatic clone during startup · F395 Acceptance test/confirmation pending |
| Siemens SINAMICS G120 | F01040 Parameters must be saved · F01044 Error loading data from memory card · F01105 CU: Insufficient memory · F13100 Know-how protection: Copy protection error · F13101 Know-how protection: Copy protection cannot be activated · A01101 Memory card not available |
| Siemens SINAMICS V90 | A1019 Writing to the removable data medium unsuccessful · A1032 All parameters must be saved · A1045 Configuring data invalid · A52900 Failure during data copying |
| Siemens MICROMASTER 440 | F0051 Parameter EEPROM fault |
| Allen-Bradley PowerFlex 525 | F048 Params Defaulted · F100 Parameter Chksum · F101 External Storage |
| ABB ACS355 | A5010 Corrupted panel parameter backup file · A5018 Parameter default value is not found · A5025 Software is being uploaded or downloaded · A5029 Memory is not ready · A5040 Parameter download error: the selected set is not in the backup file · A5041 Parameter backup file does not fit into memory |
| Delta VFD-E | cF1.0 Power board CPU write failure · cF1.1 Control board CPU write failure · cF2.0 Power board CPU read failure · cF2.1 Control board CPU read failure |
| Delta C2000 | cF1 EEPROM write error · cF2 EEPROM read error |
| Hitachi WJ200 | E08 EEPROM error |
| Schneider Electric Altivar ATV320 | EEF1 EEprom control error · EEF2 EEprom power error |
| INVT Goodrive20 (GD20) | EEP EEPROM operation fault |
| Yaskawa V1000 | CPF06 EEPROM Data Error · Err EEPROM Write Error |
| Yaskawa A1000 | CPF06 EEPROM Memory Data Error · dWF1 EEPROM Memory DriveWorksEZ Data Error · Err EEPROM Write Error |
| Yaskawa GA500 | CPF06 Control Circuit Error (EEPROM memory Data Error) · dWF1 EEPROM Memory DWEZ Data Error · Err EEPROM Write Error · LoG Log Com Error |
| Siemens MICROMASTER 420 | F0051 Parameter EEPROM fault |
| Siemens MICROMASTER 430 | F0051 Parameter EEPROM fault · F0053 I/O EEPROM fault |
| Siemens SINAMICS G110 | F0051 Parameter EEPROM fault · F0055 BOP-EEPROM fault |
| INVT Goodrive200A (GD200A) | EEP EEPROM operation fault |
| Mitsubishi Electric FR-D700 | E.PE Parameter storage device fault (control circuit board) |
| Danfoss VLT Micro Drive FC 51 | Error 86 Copy fail · Error 87 LCP data invalid · Error 88 LCP data not compatible |
07 / More codes
Other ASDA-B2 codes
Source
Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007