F048 on the Allen-Bradley PowerFlex 525 is the “Params Defaulted” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive could not read or write its stored parameters, or found them invalid. The drive may start with wrong settings, or refuse to start.
- Code
- F048
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Parameter memory
01 / Causes
What causes F048
- The drive's parameters have been reset to their defaults.
02 / Checks
What to check for F048
In the order Rockwell Automation gives them.
- 01Clear the fault or cycle power to the drive.
- 02Program the drive parameters again as needed.
03 / Clearing it
How to clear F048
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F048 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How parameter memory faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and see whether the fault clears.
- 02If it returns, restore the parameters from a backup, or reset to factory settings and set the drive up again.
- 03Keep a parameter backup of every drive, so this never means guessing the settings.
05 / Repair
When F048 means a repair
A memory fault that survives a factory reset needs the control board repaired or replaced.
If F048 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Parameter memory: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F51 Parameter EEPROM fault · F61 SD card parameter cloning failed · F62 Parameter cloning contents invalid · F63 Parameter cloning contents incompatible · F64 Inverter attempted to do an automatic clone during startup · F395 Acceptance test/confirmation pending |
| Siemens SINAMICS G120 | F01040 Parameters must be saved · F01044 Error loading data from memory card · F01105 CU: Insufficient memory · F13100 Know-how protection: Copy protection error · F13101 Know-how protection: Copy protection cannot be activated · A01101 Memory card not available |
| Siemens SINAMICS V90 | A1019 Writing to the removable data medium unsuccessful · A1032 All parameters must be saved · A1045 Configuring data invalid · A52900 Failure during data copying |
| Siemens MICROMASTER 440 | F0051 Parameter EEPROM fault |
| ABB ACS355 | A5010 Corrupted panel parameter backup file · A5018 Parameter default value is not found · A5025 Software is being uploaded or downloaded · A5029 Memory is not ready · A5040 Parameter download error: the selected set is not in the backup file · A5041 Parameter backup file does not fit into memory |
| Delta VFD-E | cF1.0 Power board CPU write failure · cF1.1 Control board CPU write failure · cF2.0 Power board CPU read failure · cF2.1 Control board CPU read failure |
| Delta C2000 | cF1 EEPROM write error · cF2 EEPROM read error |
| Delta ASDA-B2 | AL017 Abnormal EEPROM · AL099 DSP firmware upgrade |
| Hitachi WJ200 | E08 EEPROM error |
| Schneider Electric Altivar ATV320 | EEF1 EEprom control error · EEF2 EEprom power error |
| INVT Goodrive20 (GD20) | EEP EEPROM operation fault |
| Yaskawa V1000 | CPF06 EEPROM Data Error · Err EEPROM Write Error |
| Yaskawa A1000 | CPF06 EEPROM Memory Data Error · dWF1 EEPROM Memory DriveWorksEZ Data Error · Err EEPROM Write Error |
| Yaskawa GA500 | CPF06 Control Circuit Error (EEPROM memory Data Error) · dWF1 EEPROM Memory DWEZ Data Error · Err EEPROM Write Error · LoG Log Com Error |
| Siemens MICROMASTER 420 | F0051 Parameter EEPROM fault |
| Siemens MICROMASTER 430 | F0051 Parameter EEPROM fault · F0053 I/O EEPROM fault |
| Siemens SINAMICS G110 | F0051 Parameter EEPROM fault · F0055 BOP-EEPROM fault |
| INVT Goodrive200A (GD200A) | EEP EEPROM operation fault |
| Mitsubishi Electric FR-D700 | E.PE Parameter storage device fault (control circuit board) |
| Danfoss VLT Micro Drive FC 51 | Error 86 Copy fail · Error 87 LCP data invalid · Error 88 LCP data not compatible |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007