SINAMICS V20 A511: Motor overtemperature I2t

A511 on the Siemens SINAMICS V20 is the “Motor overtemperature I2t” alarm. An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.

Code
A511
Type
Alarm (warning)
Drive
Siemens SINAMICS V20
Kind of fault
Motor overload or overtemperature

01 / Causes

What causes A511

  • The motor is overloaded.
  • Load cycles or load steps are too high.

02 / Checks

What to check for A511

In the order Siemens gives them.

  1. 01Check the motor temperature warning threshold (P0604) and the motor's surrounding temperature (P0625).
  2. 02Check the rating plate data entered; if it is wrong, run quick commissioning. Motor identification (P1900 = 2) gives accurate data.
  3. 03Check the motor weight (P0344) is reasonable.
  4. 04For a motor that is not a standard Siemens motor, the overtemperature limits can be changed with P0626 to P0628.

03 / Clearing it

How to clear A511

An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

If A511 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How motor overload or overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare running current with the motor's rating plate current.
  2. 02Check the motor overload settings in the drive against the rating plate.
  3. 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
  4. 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.

05 / Repair

When A511 means a repair

A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.

If A511 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Motor overload or overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature
Siemens SINAMICS V90F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature
Siemens MICROMASTER 440F0011 Motor overtemperature · A0511 Motor overtemperature
Allen-Bradley PowerFlex 525F007 Motor Overload
ABB ACS355F0009 MOT OVERTEMP · A2010 MOTOR TEMP
Delta VFD-EoL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection
Delta C2000EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating
Delta ASDA-B2AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload
Hitachi WJ200E05 Overload protection · E35 Thermistor
Schneider Electric Altivar ATV320OLF Motor overload error · OTFL DI6=PTC overheat error
INVT Goodrive20 (GD20)OL1 Motor overload
Yaskawa V1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Yaskawa A1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload
Yaskawa GA500oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Siemens MICROMASTER 420F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t
Siemens MICROMASTER 430F0011 Motor overtemperature · A0511 Motor overtemperature
Siemens SINAMICS G110F0011 Motor over temperature I2t · A0511 Motor over temperature I2t
INVT Goodrive200A (GD200A)OL1 Motor overload
Mitsubishi Electric FR-D700E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 10 Motor ETR over temperature

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

A511 won't clear? Get a technician who knows the SINAMICS V20.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.