SINAMICS V20 A952: Load monitoring warning

A952 on the Siemens SINAMICS V20 is the “Load monitoring warning” alarm. An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.

Code
A952
Type
Alarm (warning)
Drive
Siemens SINAMICS V20
Kind of fault
Load monitoring

01 / Causes

What causes A952

  • The load on the motor indicates a belt failure or mechanical fault.

02 / Checks

What to check for A952

In the order Siemens gives them.

  1. 01Siemens refers to the F452 checks: inspect the drive train, then the monitoring thresholds.

03 / Clearing it

How to clear A952

An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.

If A952 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How load monitoring faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the mechanics: belts, couplings, gearbox and the driven machine.
  2. 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.

05 / Repair

When A952 means a repair

Usually a mechanical repair on the machine, not the drive.

If A952 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Load monitoring: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high
Siemens SINAMICS V90F7901 Motor overspeed
Siemens MICROMASTER 440F0452 Load torque fault detected · A0952 Load fault detected
Allen-Bradley PowerFlex 525F015 Load Loss
ABB ACS355F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD
Delta C2000ot1 Over torque 1 · ot2 Over torque 2 · uC Under current
Delta ASDA-B2AL007 Over speed · AL030 Motor crash error
Hitachi WJ200E81 Excessive speed
Schneider Electric Altivar ATV320DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error
INVT Goodrive20 (GD20)OL3 Electronic overload · LL Electronic underload fault
Yaskawa V1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa A1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa GA500oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Siemens MICROMASTER 420F0422 No load applied to inverter · A0922 No load at the inverter
Siemens MICROMASTER 430F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected
INVT Goodrive200A (GD200A)OL3 Electronic overload fault · LL Electronic underload fault
Mitsubishi Electric FR-D700E.CDO Output current detection value exceeded

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

A952 won't clear? Get a technician who knows the SINAMICS V20.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.