F015 on the Allen-Bradley PowerFlex 525 is the “Load Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.
- Code
- F015
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Load monitoring
01 / Causes
What causes F015
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing load monitoring faults explains where it usually comes from.
02 / Checks
What to check for F015
In the order Rockwell Automation gives them.
- 01Check the connection between the motor and the load.
- 02Check the level and time settings for load loss detection.
Also in the manual
- This fault does not apply to the PowerFlex 523, only the PowerFlex 525.
03 / Clearing it
How to clear F015
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F015 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How load monitoring faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the mechanics: belts, couplings, gearbox and the driven machine.
- 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.
05 / Repair
When F015 means a repair
Usually a mechanical repair on the machine, not the drive.
If F015 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Load monitoring: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F452 Load monitoring trip · A952 Load monitoring warning |
| Siemens SINAMICS G120 | F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high |
| Siemens SINAMICS V90 | F7901 Motor overspeed |
| Siemens MICROMASTER 440 | F0452 Load torque fault detected · A0952 Load fault detected |
| ABB ACS355 | F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD |
| Delta C2000 | ot1 Over torque 1 · ot2 Over torque 2 · uC Under current |
| Delta ASDA-B2 | AL007 Over speed · AL030 Motor crash error |
| Hitachi WJ200 | E81 Excessive speed |
| Schneider Electric Altivar ATV320 | DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error |
| INVT Goodrive20 (GD20) | OL3 Electronic overload · LL Electronic underload fault |
| Yaskawa V1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa A1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa GA500 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Siemens MICROMASTER 420 | F0422 No load applied to inverter · A0922 No load at the inverter |
| Siemens MICROMASTER 430 | F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected |
| INVT Goodrive200A (GD200A) | OL3 Electronic overload fault · LL Electronic underload fault |
| Mitsubishi Electric FR-D700 | E.CDO Output current detection value exceeded |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.