PowerFlex 525 F015: Load Loss

F015 on the Allen-Bradley PowerFlex 525 is the “Load Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.

Code
F015
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Load monitoring

01 / Causes

What causes F015

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing load monitoring faults explains where it usually comes from.

02 / Checks

What to check for F015

In the order Rockwell Automation gives them.

  1. 01Check the connection between the motor and the load.
  2. 02Check the level and time settings for load loss detection.

Also in the manual

  • This fault does not apply to the PowerFlex 523, only the PowerFlex 525.

03 / Clearing it

How to clear F015

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F015 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How load monitoring faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the mechanics: belts, couplings, gearbox and the driven machine.
  2. 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.

05 / Repair

When F015 means a repair

Usually a mechanical repair on the machine, not the drive.

If F015 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Load monitoring: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F452 Load monitoring trip · A952 Load monitoring warning
Siemens SINAMICS G120F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high
Siemens SINAMICS V90F7901 Motor overspeed
Siemens MICROMASTER 440F0452 Load torque fault detected · A0952 Load fault detected
ABB ACS355F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD
Delta C2000ot1 Over torque 1 · ot2 Over torque 2 · uC Under current
Delta ASDA-B2AL007 Over speed · AL030 Motor crash error
Hitachi WJ200E81 Excessive speed
Schneider Electric Altivar ATV320DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error
INVT Goodrive20 (GD20)OL3 Electronic overload · LL Electronic underload fault
Yaskawa V1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa A1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa GA500oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Siemens MICROMASTER 420F0422 No load applied to inverter · A0922 No load at the inverter
Siemens MICROMASTER 430F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected
INVT Goodrive200A (GD200A)OL3 Electronic overload fault · LL Electronic underload fault
Mitsubishi Electric FR-D700E.CDO Output current detection value exceeded

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F015 won't clear? Get a technician who knows the PowerFlex 525.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.