MachineryFix

Yaskawa AC drive (VFD) · fault code

A1000 UL3: Undertorque Detection 1

UL3 on the Yaskawa A1000 is the “Undertorque Detection 1” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.

The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.

Code
UL3
Type
Fault (stops the drive)
Drive
Yaskawa A1000
Kind of fault
Load monitoring

01 / Causes

What causes UL3

  • The current stayed below Torque Detection Level 1 (L6-02) for longer than L6-03: settings that do not suit the load, or a fault on the machine side.

02 / Checks

What to check for UL3

In the order Yaskawa gives them.

  1. 01Check L6-02 and L6-03.
  2. 02Check the load for problems.

Also in the manual

  • The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.

03 / Clearing it

How to clear UL3

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

Clear it once. If UL3 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How load monitoring faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the mechanics: belts, couplings, gearbox and the driven machine.
  2. 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.

05 / Repair

When UL3 means a repair

Usually a mechanical repair on the machine, not the drive.

If UL3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Load monitoring: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F452 Load monitoring trip · A952 Load monitoring warning
Siemens SINAMICS G120F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high
Siemens SINAMICS V90F7901 Motor overspeed
Siemens MICROMASTER 440F0452 Load torque fault detected · A0952 Load fault detected
Allen-Bradley PowerFlex 525F015 Load Loss
ABB ACS355F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD
Delta C2000ot1 Over torque 1 · ot2 Over torque 2 · uC Under current
Delta ASDA-B2AL007 Over speed · AL030 Motor crash error
Hitachi WJ200E81 Excessive speed
Schneider Electric Altivar ATV320DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error
INVT Goodrive20 (GD20)OL3 Electronic overload · LL Electronic underload fault
Yaskawa V1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa GA500oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Siemens MICROMASTER 420F0422 No load applied to inverter · A0922 No load at the inverter
Siemens MICROMASTER 430F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected
INVT Goodrive200A (GD200A)OL3 Electronic overload fault · LL Electronic underload fault
Mitsubishi Electric FR-D700E.CDO Output current detection value exceeded

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

UL3 won't clear? Get a technician who knows the A1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.