oL3 on the Yaskawa A1000 is the “Overtorque Detection 1” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.
The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.
- Code
- oL3
- Type
- Fault (stops the drive)
- Drive
- Yaskawa A1000
- Kind of fault
- Load monitoring
01 / Causes
What causes oL3
- The current stayed above Torque Detection Level 1 (L6-02) for longer than L6-03: settings that do not suit the load, or a locked-up machine.
02 / Checks
What to check for oL3
In the order Yaskawa gives them.
- 01Check L6-02 and L6-03.
- 02Check the load and remove the cause of the fault.
Also in the manual
- The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.
03 / Clearing it
How to clear oL3
- Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
- Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.
Clear it once. If oL3 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How load monitoring faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the mechanics: belts, couplings, gearbox and the driven machine.
- 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.
05 / Repair
When oL3 means a repair
Usually a mechanical repair on the machine, not the drive.
If oL3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Load monitoring: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F452 Load monitoring trip · A952 Load monitoring warning |
| Siemens SINAMICS G120 | F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high |
| Siemens SINAMICS V90 | F7901 Motor overspeed |
| Siemens MICROMASTER 440 | F0452 Load torque fault detected · A0952 Load fault detected |
| Allen-Bradley PowerFlex 525 | F015 Load Loss |
| ABB ACS355 | F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD |
| Delta C2000 | ot1 Over torque 1 · ot2 Over torque 2 · uC Under current |
| Delta ASDA-B2 | AL007 Over speed · AL030 Motor crash error |
| Hitachi WJ200 | E81 Excessive speed |
| Schneider Electric Altivar ATV320 | DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error |
| INVT Goodrive20 (GD20) | OL3 Electronic overload · LL Electronic underload fault |
| Yaskawa V1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa GA500 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Siemens MICROMASTER 420 | F0422 No load applied to inverter · A0922 No load at the inverter |
| Siemens MICROMASTER 430 | F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected |
| INVT Goodrive200A (GD200A) | OL3 Electronic overload fault · LL Electronic underload fault |
| Mitsubishi Electric FR-D700 | E.CDO Output current detection value exceeded |
07 / More codes
Other A1000 codes
Source
Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007