Delta AC drive (VFD) · fault code

C2000 ot2: Over torque 2

ot2 on the Delta C2000 is the “Over torque 2” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.

Code
ot2
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Load monitoring

01 / Causes

What causes ot2

  • Pr. 06-07 and Pr. 06-08 (detection level and time) set wrongly.
  • A mechanical fault such as a jam or a lock.
  • The load is too large, or the motor is too small.
  • The acceleration or deceleration time, or the working cycle, is too short.
  • The V/F voltage is too high.
  • Overload during low-speed running.
  • Torque compensation too large.
  • Speed tracking set wrongly (including restart after a momentary power loss or after a fault).

02 / Checks

What to check for ot2

In the order Delta Electronics gives them.

  1. 01Set the over-torque detection level and time again.
  2. 02Remove the mechanical cause.
  3. 03Reduce the load, or fit a larger motor.
  4. 04Lengthen the acceleration and deceleration times (Pr. 01-12 to 01-19).
  5. 05Adjust the V/F curve (Pr. 01-01 to 01-08), especially the mid-point voltage, and see the V/F curve selection in Pr. 01-43. A mid-point voltage set too low reduces the load capacity at low speed.
  6. 06Shorten low-speed running, or use a larger motor.
  7. 07Lower the torque compensation gain (Pr. 07-26) until the output current drops and the motor does not stall.
  8. 08Correct the speed tracking settings: turn on speed tracking, and adjust its maximum current (Pr. 07-09).

Also in the manual

  • Fault ID 27. The output current stayed above Pr. 06-10 for longer than Pr. 06-11.
  • Pr. 06-09 sets the response: at 2 or 4 the drive stops and ot2 is a fault, reset manually; at 1 or 3 it is a warning that clears once the current is 5% below Pr. 06-10.

03 / Clearing it

How to clear ot2

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If ot2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How load monitoring faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the mechanics: belts, couplings, gearbox and the driven machine.
  2. 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.

05 / Repair

When ot2 means a repair

Usually a mechanical repair on the machine, not the drive.

If ot2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Load monitoring: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F452 Load monitoring trip · A952 Load monitoring warning
Siemens SINAMICS G120F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high
Siemens SINAMICS V90F7901 Motor overspeed
Siemens MICROMASTER 440F0452 Load torque fault detected · A0952 Load fault detected
Allen-Bradley PowerFlex 525F015 Load Loss
ABB ACS355F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD
Delta ASDA-B2AL007 Over speed · AL030 Motor crash error
Hitachi WJ200E81 Excessive speed
Schneider Electric Altivar ATV320DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error
INVT Goodrive20 (GD20)OL3 Electronic overload · LL Electronic underload fault
Yaskawa V1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa A1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa GA500oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Siemens MICROMASTER 420F0422 No load applied to inverter · A0922 No load at the inverter
Siemens MICROMASTER 430F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected
INVT Goodrive200A (GD200A)OL3 Electronic overload fault · LL Electronic underload fault
Mitsubishi Electric FR-D700E.CDO Output current detection value exceeded

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

ot2 won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.