Delta Servo drive · alarm code

ASDA-B2 AL007: Over speed

AL007 on the Delta ASDA-B2 is the “Over speed” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.

The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.

Code
AL007
Type
Alarm (stops the drive)
Drive
Delta ASDA-B2
Kind of fault
Load monitoring

01 / Causes

What causes AL007

  • An unreasonable command.
  • The over-speed warning condition (P2-34) is set too small.
  • A torque limit is active.

02 / Checks

What to check for AL007

In the order Delta Electronics gives them.

  1. 01Check the analog voltage command with a scope; use a less steep command, or a filter to smooth it.
  2. 02Set P2-34 (the over-speed warning condition) correctly.
  3. 03Check whether the torque limit input (DI.TRQLM), the default torque limit in P1-02, or a limit in P1-12 to P1-14 is active; disable the input or the default, or set P1-12 to P1-14 to 100%.

Also in the manual

  • The motor's speed exceeds the normal speed. ALM output; servo off. Clears by turning on the alarm reset input (DI.ARST).

03 / Clearing it

How to clear AL007

  • Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
  • Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
  • AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
  • AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.

Clear it once. If AL007 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How load monitoring faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the mechanics: belts, couplings, gearbox and the driven machine.
  2. 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.

05 / Repair

When AL007 means a repair

Usually a mechanical repair on the machine, not the drive.

If AL007 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Load monitoring: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F452 Load monitoring trip · A952 Load monitoring warning
Siemens SINAMICS G120F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high
Siemens SINAMICS V90F7901 Motor overspeed
Siemens MICROMASTER 440F0452 Load torque fault detected · A0952 Load fault detected
Allen-Bradley PowerFlex 525F015 Load Loss
ABB ACS355F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD
Delta C2000ot1 Over torque 1 · ot2 Over torque 2 · uC Under current
Hitachi WJ200E81 Excessive speed
Schneider Electric Altivar ATV320DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error
INVT Goodrive20 (GD20)OL3 Electronic overload · LL Electronic underload fault
Yaskawa V1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa A1000oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Yaskawa GA500oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2
Siemens MICROMASTER 420F0422 No load applied to inverter · A0922 No load at the inverter
Siemens MICROMASTER 430F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected
INVT Goodrive200A (GD200A)OL3 Electronic overload fault · LL Electronic underload fault
Mitsubishi Electric FR-D700E.CDO Output current detection value exceeded

07 / More codes

Other ASDA-B2 codes

Source

Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

AL007 won't clear? Get a technician who knows the ASDA-B2.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.