F452 on the Siemens SINAMICS V20 is the “Load monitoring trip” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.
The drive's load monitor saw torque or speed outside the band set for this machine: a broken belt, a dry-running pump or a jam.
- Code
- F452
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V20
- Kind of fault
- Load monitoring
01 / Causes
What causes F452
- The load on the motor indicates a belt failure or a mechanical fault.
- r0949 = 0: tripped on low torque or speed; r0949 = 1: tripped on high torque or speed.
02 / Checks
What to check for F452
In the order Siemens gives them.
- 01Check for breakage, seizure or obstruction in the drive train, and lubricate if needed.
- 02With an external speed sensor, check P2192 and the threshold frequencies P2182 to P2184.
- 03With a torque or speed band, check the thresholds P2182 to P2190 and the delay P2192.
03 / Clearing it
How to clear F452
- Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
- Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
- Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.
Clear it once. If F452 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How load monitoring faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the mechanics: belts, couplings, gearbox and the driven machine.
- 02Check the monitoring thresholds and delay set in the drive against the machine's normal load.
05 / Repair
When F452 means a repair
Usually a mechanical repair on the machine, not the drive.
If F452 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Load monitoring: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07894 Load monitoring, pump/fan blocked · F07895 Load monitoring, pump/fan without load · F07896 Load monitoring, pump leakage · F07901 Motor overspeed · F07923 Torque/speed too low · F07924 Torque/speed too high |
| Siemens SINAMICS V90 | F7901 Motor overspeed |
| Siemens MICROMASTER 440 | F0452 Load torque fault detected · A0952 Load fault detected |
| Allen-Bradley PowerFlex 525 | F015 Load Loss |
| ABB ACS355 | F0017 UNDERLOAD · F0024 OVERSPEED · A2011 UNDERLOAD |
| Delta C2000 | ot1 Over torque 1 · ot2 Over torque 2 · uC Under current |
| Delta ASDA-B2 | AL007 Over speed · AL030 Motor crash error |
| Hitachi WJ200 | E81 Excessive speed |
| Schneider Electric Altivar ATV320 | DLF Dynamic load detected error · OLC Process overload error · SOF Motor overspeed error · ULF Process underload error |
| INVT Goodrive20 (GD20) | OL3 Electronic overload · LL Electronic underload fault |
| Yaskawa V1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa A1000 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Yaskawa GA500 | oL3 Overtorque Detection 1 · oL4 Overtorque Detection 2 · oL5 Mechanical Weakening Detection 1 · UL3 Undertorque Detection 1 · UL4 Undertorque Detection 2 · UL5 Mechanical Weakening Detection 2 |
| Siemens MICROMASTER 420 | F0422 No load applied to inverter · A0922 No load at the inverter |
| Siemens MICROMASTER 430 | F0422 No load applied to inverter · F0452 Load torque fault detected · A0922 No load at the inverter · A0952 Load fault detected |
| INVT Goodrive200A (GD200A) | OL3 Electronic overload fault · LL Electronic underload fault |
| Mitsubishi Electric FR-D700 | E.CDO Output current detection value exceeded |
07 / More codes
Other SINAMICS V20 codes
Source
Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007