oL2 on the Yaskawa A1000 is the “Drive Overload” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.
The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.
- Code
- oL2
- Type
- Fault (stops the drive)
- Drive
- Yaskawa A1000
- Kind of fault
- Drive overload
01 / Causes
What causes oL2
- The drive's thermal sensor triggered its overload protection: too heavy a load, short acceleration or deceleration, an unsuitable V/f pattern, a drive too small, overload at low speed, too much torque compensation, wrong Speed Search settings, or an input phase loss.
02 / Checks
What to check for oL2
In the order Yaskawa gives them.
- 01Reduce the load, especially at low speed, and lengthen C1-01 to C1-08.
- 02Set the V/f pattern parameters (E1-04 to E1-10) to match the motor.
- 03Use a larger drive, or one frame size larger for low-speed duty, and lower the carrier frequency (C6-02).
- 04Reduce the torque compensation gain (C4-01).
- 05Check the Speed Search settings and, after Auto-Tuning, set b3-24 to 1.
- 06Check the supply for a missing phase.
03 / Clearing it
How to clear oL2
- Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
- Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.
Clear it once. If oL2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overload faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Record the running current and compare it with the drive's rated current.
- 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
- 03Check acceleration time and boost settings; long periods at high torque add up quickly.
05 / Repair
When oL2 means a repair
If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.
If oL2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Drive overload: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F5 Inverter I2t · A505 Inverter I2t |
| Siemens SINAMICS G120 | F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t |
| Siemens SINAMICS V90 | F30005 Power unit: Overload I2t |
| Siemens MICROMASTER 440 | F0005 Inverter I2T · A0505 Inverter I2T |
| Allen-Bradley PowerFlex 525 | F064 Drive Overload |
| Delta VFD-E | oL Overload |
| Delta C2000 | oL Over load · oL3 Overload protection at low frequency |
| Hitachi WJ200 | E38 Low-speed overload protection |
| INVT Goodrive20 (GD20) | OL2 VFD overload |
| Yaskawa V1000 | oL2 Drive Overload |
| Yaskawa GA500 | oL2 Drive Overload |
| Siemens MICROMASTER 420 | F0005 Inverter I2t · A0505 Inverter I2t |
| Siemens MICROMASTER 430 | F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle |
| Siemens SINAMICS G110 | F0005 Inverter I2t · A0505 Inverter I2t |
| INVT Goodrive200A (GD200A) | OL2 VFD overload |
| Mitsubishi Electric FR-D700 | E.THT Inverter overload trip (electronic thermal O/L relay function) |
| Danfoss VLT Micro Drive FC 51 | Alarm 9 Inverter overloaded |
07 / More codes
Other A1000 codes
Source
Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.