A1000 EF5: External Fault (input terminal S5)

EF5 on the Yaskawa A1000 is the “External Fault (input terminal S5)” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.

Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.

Code
EF5
Type
Fault (stops the drive)
Drive
Yaskawa A1000
Kind of fault
External fault

01 / Causes

What causes EF5

  • An external device tripped an alarm through multi-function input S5, the signal is wired to the wrong terminal, or an unused terminal is set as an external fault input.

02 / Checks

What to check for EF5

In the order Yaskawa gives them.

  1. 01Remove the cause of the external fault and reset the fault.
  2. 02Connect the signal to the terminal assigned to external fault detection (H1-oo = 20 to 2B).
  3. 03Check no unused terminal is set to an external fault function (H1-oo = 20 to 2B), and change it if so.

Also in the manual

  • The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.

03 / Clearing it

How to clear EF5

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

Clear it once. If EF5 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How external fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Find which input or control word is set as the external fault source in the drive's parameters.
  2. 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.

05 / Repair

When EF5 means a repair

The fix is usually on the device that raised the input, not in the drive.

If EF5 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

External fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F85 External fault
Siemens SINAMICS G120F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3
Siemens MICROMASTER 440F0085 External fault
Allen-Bradley PowerFlex 525F002 Auxiliary Input · F094 Function Loss
ABB ACS355F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING
Delta VFD-EEF External fault
Delta C2000LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error
Hitachi WJ200E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3
Schneider Electric Altivar ATV320BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error
INVT Goodrive20 (GD20)EF External fault
Yaskawa V1000dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) · EF4 External Fault (input terminal S4)
Yaskawa GA500dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2)
Siemens MICROMASTER 420F0085 External fault
Siemens MICROMASTER 430F0085 External fault
Siemens SINAMICS G110F0085 External fault
INVT Goodrive200A (GD200A)EF External fault
Mitsubishi Electric FR-D700E.OHT External thermal relay operation · PS PU stop

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

EF5 won't clear? Get a technician who knows the A1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.