Yaskawa AC drive (VFD) · fault code

A1000 oH: Heatsink Overheat

oH on the Yaskawa A1000 is the “Heatsink Overheat” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.

The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.

Code
oH
Type
Fault (stops the drive)
Drive
Yaskawa A1000
Kind of fault
Drive overtemperature

01 / Causes

What causes oH

  • The heatsink temperature went above the pre-alarm level in L8-02 (default set by drive model, o2-04): surrounding temperature too high, too heavy a load, or the internal fan stopped.

02 / Checks

What to check for oH

In the order Yaskawa gives them.

  1. 01Check the temperature around the drive; improve the panel's air circulation, add cooling, and remove nearby heat sources.
  2. 02Measure the output current, reduce the load and lower the carrier frequency (C6-02).
  3. 03Replace a stopped fan, then set o4-03 to 0.

Also in the manual

  • The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.

03 / Clearing it

How to clear oH

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

Clear it once. If oH comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
  2. 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
  3. 03Measure the temperature inside the panel and check the panel fans and filters.
  4. 04Check the switching frequency against the factory setting and the load current against the drive's rating.

05 / Repair

When oH means a repair

A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.

If oH keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Drive overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning
Siemens SINAMICS G120F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature
Siemens SINAMICS V90F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature
Siemens MICROMASTER 440F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high
Allen-Bradley PowerFlex 525F008 Heatsink OvrTmp · F009 CC OvrTmp
ABB ACS355F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP
Delta VFD-EoH1 IGBT overheat · oH2 Power board overheat
Delta C2000oH1 IGBT overheating · oH2 Heatsink overheating
Delta ASDA-B2AL016 IGBT overheat
Hitachi WJ200E21 Inverter thermal trip
Schneider Electric Altivar ATV320OHF Drive overheating error · TJF IGBT overheating
INVT Goodrive20 (GD20)OH1 Rectifier module overheat · OH2 Inverter module overheat
Yaskawa V1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat)
Yaskawa GA500oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B)
Siemens MICROMASTER 420F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens MICROMASTER 430F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens SINAMICS G110F0004 Inverter over temperature
INVT Goodrive200A (GD200A)OH1 Rectifier module overheating · OH2 Inverter module overheat
Mitsubishi Electric FR-D700E.FIN Heatsink overheat
Danfoss VLT Micro Drive FC 51Alarm 29 Heat sink temperature

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.