MachineryFix

Yaskawa AC drive (VFD) · fault code

A1000 oL1: Motor Overload

oL1 on the Yaskawa A1000 is the “Motor Overload” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.

The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.

Code
oL1
Type
Fault (stops the drive)
Drive
Yaskawa A1000
Kind of fault
Motor overload or overtemperature

01 / Causes

What causes oL1

  • The electronic motor overload protection tripped.
  • Too heavy a load, short acceleration and deceleration cycles, a general-purpose motor run below rated speed under heavy load, an unsuitable V/f pattern, a wrong E2-01, several motors on one drive, the wrong protection type, overexcitation, wrong Speed Search settings, or an input phase loss.

02 / Checks

What to check for oL1

In the order Yaskawa gives them.

  1. 01Reduce the load and lengthen C1-01 to C1-08.
  2. 02For sustained low-speed duty, increase the speed, use a larger motor, or use a motor designed for that speed range.
  3. 03Set the V/f pattern parameters (E1-04 to E1-10) to match the motor.
  4. 04Enter the nameplate rated current in E2-01.
  5. 05With several motors on one drive, set L1-01 to 0 and fit a thermal relay to each motor; otherwise correct the motor protection type in L1-01.
  6. 06Limit overexcitation: reduce n3-13, set L3-04 to something other than 4, or set n3-23 to 0.
  7. 07Check the Speed Search settings (b3-02, b3-03) and, after Auto-Tuning, set b3-24 to 1.
  8. 08Check the supply for a missing phase.

Also in the manual

  • oL1 can only be reset once monitor U4-16 is below 100.0%.

03 / Clearing it

How to clear oL1

  • Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
  • Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.

Clear it once. If oL1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor overload or overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare running current with the motor's rating plate current.
  2. 02Check the motor overload settings in the drive against the rating plate.
  3. 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
  4. 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.

05 / Repair

When oL1 means a repair

A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.

If oL1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor overload or overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F11 Motor overtemperature · A511 Motor overtemperature I2t
Siemens SINAMICS G120F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature
Siemens SINAMICS V90F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature
Siemens MICROMASTER 440F0011 Motor overtemperature · A0511 Motor overtemperature
Allen-Bradley PowerFlex 525F007 Motor Overload
ABB ACS355F0009 MOT OVERTEMP · A2010 MOTOR TEMP
Delta VFD-EoL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection
Delta C2000EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating
Delta ASDA-B2AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload
Hitachi WJ200E05 Overload protection · E35 Thermistor
Schneider Electric Altivar ATV320OLF Motor overload error · OTFL DI6=PTC overheat error
INVT Goodrive20 (GD20)OL1 Motor overload
Yaskawa V1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Yaskawa GA500oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Siemens MICROMASTER 420F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t
Siemens MICROMASTER 430F0011 Motor overtemperature · A0511 Motor overtemperature
Siemens SINAMICS G110F0011 Motor over temperature I2t · A0511 Motor over temperature I2t
INVT Goodrive200A (GD200A)OL1 Motor overload
Mitsubishi Electric FR-D700E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 10 Motor ETR over temperature

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oL1 won't clear? Get a technician who knows the A1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.