Yaskawa AC drive (VFD) · alarm code

A1000 Uv: Undervoltage

Uv on the Yaskawa A1000 is the “Undervoltage” alarm. An alarm is a protection function that does not necessarily stop the drive: the ALM light blinks and the code flashes, and a multi-function output set to H2-oo = 10 closes. Once the cause is removed, the drive returns to the state it was in before the alarm.

The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.

Code
Uv
Type
Alarm (warning)
Drive
Yaskawa A1000
Kind of fault
DC bus undervoltage

01 / Causes

What causes Uv

  • With the drive stopped and a run command entered, the DC bus voltage was below L2-05, the inrush suppression contactor was open, or the control power was low (output only if L2-01 is not 0).
  • A missing input phase, loose input terminals, a supply voltage problem, worn internal circuitry, a supply transformer too small (voltage dips at power-on), air inside the drive too hot, or a broken CHARGE light.

02 / Checks

What to check for Uv

In the order Yaskawa gives them.

  1. 01Check and correct the main circuit input wiring, and tighten the terminals to the torque in the manual.
  2. 02Check the supply voltage is within the drive's specification.
  3. 03Check the capacitor maintenance time (U4-05); replace the control board or the drive above 90%.
  4. 04Check for the alarm as the magnetic contactor, line breaker and leakage breaker close, and check the supply transformer's capacity.
  5. 05Check the temperature inside the drive.

03 / Clearing it

How to clear Uv

An alarm is a protection function that does not necessarily stop the drive: the ALM light blinks and the code flashes, and a multi-function output set to H2-oo = 10 closes. Once the cause is removed, the drive returns to the state it was in before the alarm.

If Uv stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How dc bus undervoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
  2. 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
  3. 03Look for loose or heat-discoloured supply terminals.
  4. 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.

05 / Repair

When Uv means a repair

A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.

If Uv keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

DC bus undervoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active
Siemens SINAMICS G120F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging
Siemens SINAMICS V90F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off
Siemens MICROMASTER 440F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Allen-Bradley PowerFlex 525F003 Power Loss · F004 UnderVoltage
ABB ACS355F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage
Delta VFD-ELv Low voltage · dEb Deceleration energy backup error
Delta C2000LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error
Delta ASDA-B2AL003 Under voltage
Hitachi WJ200E09 Under-voltage error
Schneider Electric Altivar ATV320USF Supply mains undervoltage error
INVT Goodrive20 (GD20)UV Bus undervoltage · PoFF System power off
Yaskawa V1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa GA500Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage
Siemens MICROMASTER 420F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Siemens MICROMASTER 430F0003 Undervoltage · A0503 Undervoltage limit value
Siemens SINAMICS G110F0003 Undervoltage · A0503 Undervoltage limit
INVT Goodrive200A (GD200A)UV Bus undervoltage · PoFF System power failure
Mitsubishi Electric FR-D700UV Undervoltage
Danfoss VLT Micro Drive FC 51Alarm 8 DC under voltage

07 / More codes

Other A1000 codes

Source

Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.