PF on the Yaskawa A1000 is the “Input Phase Loss” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.
One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.
- Code
- PF
- Type
- Fault (stops the drive)
- Drive
- Yaskawa A1000
- Kind of fault
- Input phase loss
01 / Causes
What causes PF
- The input supply has an open phase or a large voltage imbalance (detected when L8-05 = 1): a missing phase, loose input terminals, large supply fluctuations, poor phase balance, or worn main circuit capacitors.
02 / Checks
What to check for PF
In the order Yaskawa gives them.
- 01Check and correct the main circuit input wiring.
- 02Tighten the input terminals to the torque in the manual.
- 03Check the supply voltage and stabilise it, or disable phase loss detection where the imbalance cannot be fixed.
- 04Check the capacitor maintenance time (U4-05) and replace the main capacitors if it is above 90%.
- 05If the supply is normal and the fault continues, replace the control board or the drive.
03 / Clearing it
How to clear PF
- Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
- Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.
Clear it once. If PF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How input phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure all three phases at the drive input terminals with the drive running under load.
- 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
- 03Tighten and inspect supply terminals for heat damage.
05 / Repair
When PF means a repair
If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.
If PF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Input phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F20 DC ripple too high |
| Siemens SINAMICS G120 | F30011 Line phase failure |
| Siemens SINAMICS V90 | F30011 Line phase failure in main circuit |
| Siemens MICROMASTER 440 | F0020 Line supply phase missing |
| ABB ACS355 | F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS |
| Delta VFD-E | PHL Phase loss |
| Delta C2000 | OrP Phase loss protection |
| Delta ASDA-B2 | AL022 Main circuit power lack phase |
| Schneider Electric Altivar ATV320 | PHF Input phase loss error |
| INVT Goodrive20 (GD20) | SPI Phase loss on input side |
| Yaskawa V1000 | PF Input Phase Loss |
| Yaskawa GA500 | PF Input Phase Loss |
| Siemens MICROMASTER 430 | F0020 Line supply phase missing |
| INVT Goodrive200A (GD200A) | SPI Phase loss on input side |
| Mitsubishi Electric FR-D700 | E.ILF Input phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 4 Mains phase loss |
07 / More codes
Other A1000 codes
Source
Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.