EF5 on the Yaskawa V1000 is the “External Fault (input terminal S5)” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
Something outside the drive told it to stop: a digital input or a control word bit set up as a fault input. The drive is reporting another device's trip.
- Code
- EF5
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- External fault
01 / Causes
What causes EF5
- An external device tripped an alarm through multi-function input S5.
- The signal is wired to the wrong terminal, or an unused terminal is set as an external fault input.
02 / Checks
What to check for EF5
In the order Yaskawa gives them.
- 01Remove the cause of the external fault and reset the fault.
- 02Check the signal line is connected to the terminal assigned to external fault detection (H1-oo = 20 to 2F).
- 03Check no unused terminal is set to an external fault function (H1-oo = 20 to 2F), and change the setting if so.
Also in the manual
- The V1000 can also show this code as a minor fault: the ALM LED flashes instead of staying lit, and the motor keeps running.
03 / Clearing it
How to clear EF5
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If EF5 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How external fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Find which input or control word is set as the external fault source in the drive's parameters.
- 02Trace that input to the device driving it (a thermal switch, pressure switch, PLC output or interlock) and find out why it tripped.
05 / Repair
When EF5 means a repair
The fix is usually on the device that raised the input, not in the drive.
If EF5 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
External fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F85 External fault |
| Siemens SINAMICS G120 | F07860 External fault 1 · F07861 External fault 2 · F07862 External fault 3 · A07850 External alarm 1 · A07851 External alarm 2 · A07852 External alarm 3 |
| Siemens MICROMASTER 440 | F0085 External fault |
| Allen-Bradley PowerFlex 525 | F002 Auxiliary Input · F094 Function Loss |
| ABB ACS355 | F0014 EXT FAULT 1 · F0015 EXT FAULT 2 · F0030 FORCE TRIP · A2021 START ENABLE 1 MISSING · A2022 START ENABLE 2 MISSING |
| Delta VFD-E | EF External fault |
| Delta C2000 | LMIT Limit error · EF External fault · EF1 Emergency stop · bb External base block · ydc Y-connection / Δ-connection switch error · Brk External brake error |
| Hitachi WJ200 | E12 External trip · E36 Braking error · E50 EzSQ user trip 0 · E51 EzSQ user trip 1 · E52 EzSQ user trip 2 · E53 EzSQ user trip 3 |
| Schneider Electric Altivar ATV320 | BLF Brake control error · BRF Brake feedback error · EPF1 External error · EPF2 Fieldbus external detected error · FCF1 Output contactor closed error · FCF2 Output contactor opened error |
| INVT Goodrive20 (GD20) | EF External fault |
| Yaskawa A1000 | dWAL DriveWorksEZ Fault · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (input terminal S1) · EF2 External Fault (input terminal S2) · EF3 External Fault (input terminal S3) |
| Yaskawa GA500 | dWF2 DriveWorksEZ Fault 2 · dWF3 DriveWorksEZ Fault 3 · dWFL DriveWorksEZ Fault · EF0 Option Card External Fault · EF1 External Fault (Terminal S1) · EF2 External Fault (Terminal S2) |
| Siemens MICROMASTER 420 | F0085 External fault |
| Siemens MICROMASTER 430 | F0085 External fault |
| Siemens SINAMICS G110 | F0085 External fault |
| INVT Goodrive200A (GD200A) | EF External fault |
| Mitsubishi Electric FR-D700 | E.OHT External thermal relay operation · PS PU stop |