ov on the Yaskawa V1000 is the “Overvoltage” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.
- Code
- ov
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- DC bus overvoltage
01 / Causes
What causes ov
- The DC bus voltage went above the overvoltage level: about 410 V on 200 V class drives, about 820 V on 400 V class (740 V when E1-01 is below 400).
- Regenerative energy from a short deceleration, speed overshoot after fast acceleration, too much braking load, supply surges, a ground fault charging the DC bus, wrong Speed Search settings, or input voltage too high.
- A damaged or wrongly wired braking transistor, noise, wrong load inertia settings, braking in PM open loop vector without a resistor, or motor hunting.
02 / Checks
What to check for ov
In the order Yaskawa gives them.
- 01Lengthen the deceleration time (C1-02, C1-04, C1-06, C1-08), fit a braking resistor, and keep stall prevention during deceleration on (L3-04 = 1).
- 02Lengthen the acceleration time and the S-curves; enable overvoltage suppression (L3-11 = 1).
- 03Reduce the braking torque or use a braking option.
- 04For surges on the supply (for example a thyristor converter or power factor capacitors on the same supply), fit a DC link choke.
- 05Check the motor wiring for ground faults.
- 06Check the Speed Search settings, enable Speed Search retry (b3-19 of 1 to 10), and after line-to-line resistance Auto-Tuning enable b3-24 = 1.
- 07Check the input voltage is within the drive's specification.
- 08Check the braking transistor wiring; if the transistor is damaged, replace the drive.
- 09Check the control, main circuit and ground wiring for noise.
- 10Set the load inertia ratio (L3-25) to match the load, and adjust the hunting prevention settings (n1-02, n2-02, n2-03, n8-45, n8-47).
Also in the manual
- The V1000 can also show this code as a minor fault: the ALM LED flashes instead of staying lit, and the motor keeps running.
03 / Clearing it
How to clear ov
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If ov comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus overvoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
- 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
- 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
- 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.
05 / Repair
When ov means a repair
If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.
If ov keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
DC bus overvoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active |
| Siemens SINAMICS G120 | F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage |
| Siemens SINAMICS V90 | F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage |
| Siemens MICROMASTER 440 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Allen-Bradley PowerFlex 525 | F005 OverVoltage |
| ABB ACS355 | F0002 DC OVERVOLT · A2002 OVERVOLTAGE |
| Delta VFD-E | ov Over-voltage |
| Delta C2000 | ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop |
| Delta ASDA-B2 | AL002 Over voltage |
| Hitachi WJ200 | E07 Over-voltage protection · E15 Input over-voltage |
| Schneider Electric Altivar ATV320 | OBF DC bus overvoltage error · OSF Supply mains overvoltage error |
| INVT Goodrive20 (GD20) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Yaskawa A1000 | ov Overvoltage |
| Yaskawa GA500 | ov Overvoltage |
| Siemens MICROMASTER 420 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens MICROMASTER 430 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens SINAMICS G110 | F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active |
| INVT Goodrive200A (GD200A) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Mitsubishi Electric FR-D700 | E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage) |
| Danfoss VLT Micro Drive FC 51 | Alarm 7 DC overvoltage |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007