ACS355 F0001: OVERCURRENT

F0001 on the ABB ACS355 is the “OVERCURRENT” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.

The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.

Code
F0001
Type
Fault (stops the drive)
Drive
ABB ACS355
Kind of fault
Overcurrent

01 / Causes

What causes F0001

  • Output current went above the trip level.
  • A sudden load change or a stall, or an acceleration time that is too short.
  • Motor data entered in the drive that does not match the motor.
  • A drive or motor too small for the application.
  • Damaged motor cables, a damaged motor, or the motor connected in the wrong configuration (star or delta).
  • An internal fault in the drive, or high-frequency noise on the STO lines.

02 / Checks

What to check for F0001

In the order ABB gives them.

  1. 01Check the motor load and the mechanics for a sudden load change or a stall.
  2. 02Check the acceleration times (parameters 2202 and 2205), and whether vector control would suit the application.
  3. 03Check that the motor data in parameter group 99 matches the motor's rating plate. With vector control, run the motor ID run (9910).
  4. 04Check the drive and motor are not too small for the application.
  5. 05Check the motor, the motor cable and the connections, including the phasing and the star or delta connection.
  6. 06If the drive trips on overcurrent after a start command with no motor connected (try this in scalar control), the drive has an internal fault and needs replacing.
  7. 07Check the STO cabling and remove nearby sources of high-frequency noise.

Also in the manual

  • Over a fieldbus, the drive reports this fault as code 2310.

03 / Clearing it

How to clear F0001

  • Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
  • If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
  • Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.

Clear it once. If F0001 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How overcurrent faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
  2. 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
  3. 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
  4. 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
  5. 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.

05 / Repair

When F0001 means a repair

If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.

If F0001 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.

06 / Other drives

Overcurrent: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F1 Overcurrent · A501 Current limit
Siemens SINAMICS G120F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active
Siemens SINAMICS V90F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U
Siemens MICROMASTER 440F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value
Allen-Bradley PowerFlex 525F012 HW OverCurrent · F063 SW OverCurrent
Delta VFD-Eoc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed
Delta C2000ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop
Delta ASDA-B2AL001 Over current
Hitachi WJ200E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions
Schneider Electric Altivar ATV320OCF Overcurrent error
INVT Goodrive20 (GD20)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Yaskawa V1000oC Overcurrent · HCA Current Alarm
Yaskawa A1000oC Overcurrent · HCA Current Alarm
Yaskawa GA500oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm
Siemens MICROMASTER 420F0001 Overcurrent · A0501 Current limit value
Siemens MICROMASTER 430F0001 Overcurrent · A0501 Current limit value
Siemens SINAMICS G110F0001 Overcurrent · A0501 Current limit
INVT Goodrive200A (GD200A)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Mitsubishi Electric FR-D700E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent)
Danfoss VLT Micro Drive FC 51Alarm 13 Over current · Warning 59 Current limit

07 / More codes

Other ACS355 codes

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0001 won't clear? Get a technician who knows the ACS355.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.