F0006 on the ABB ACS355 is the “DC UNDERVOLT” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- F0006
- Type
- Fault (stops the drive)
- Drive
- ABB ACS355
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes F0006
- The DC bus voltage is not high enough.
- The undervoltage controller is turned off.
- A missing input phase or a blown fuse.
- An internal fault in the rectifier bridge.
02 / Checks
What to check for F0006
In the order ABB gives them.
- 01Check the input power supply and the fuses.
- 02Check the undervoltage controller is on (parameter 2006 UNDERVOLT CTRL).
- 03Measure the input and DC voltage with a multimeter during start, stop and running, or watch parameter 0107 DC BUS VOLTAGE, to find a missing input phase.
- 04Check the condition of the input fuses.
- 05A fault in the rectifier bridge inside the drive means the drive needs replacing.
Also in the manual
- Over a fieldbus, the drive reports this fault as code 3220.
03 / Clearing it
How to clear F0006
- Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
- If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
- Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.
Clear it once. If F0006 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When F0006 means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If F0006 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Siemens MICROMASTER 440 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta C2000 | LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error |
| Delta ASDA-B2 | AL003 Under voltage |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa V1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 420 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.