ACS355 F0006: DC UNDERVOLT

F0006 on the ABB ACS355 is the “DC UNDERVOLT” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.

The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.

Code
F0006
Type
Fault (stops the drive)
Drive
ABB ACS355
Kind of fault
DC bus undervoltage

01 / Causes

What causes F0006

  • The DC bus voltage is not high enough.
  • The undervoltage controller is turned off.
  • A missing input phase or a blown fuse.
  • An internal fault in the rectifier bridge.

02 / Checks

What to check for F0006

In the order ABB gives them.

  1. 01Check the input power supply and the fuses.
  2. 02Check the undervoltage controller is on (parameter 2006 UNDERVOLT CTRL).
  3. 03Measure the input and DC voltage with a multimeter during start, stop and running, or watch parameter 0107 DC BUS VOLTAGE, to find a missing input phase.
  4. 04Check the condition of the input fuses.
  5. 05A fault in the rectifier bridge inside the drive means the drive needs replacing.

Also in the manual

  • Over a fieldbus, the drive reports this fault as code 3220.

03 / Clearing it

How to clear F0006

  • Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
  • If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
  • Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.

Clear it once. If F0006 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How dc bus undervoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
  2. 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
  3. 03Look for loose or heat-discoloured supply terminals.
  4. 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.

05 / Repair

When F0006 means a repair

A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.

If F0006 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.

06 / Other drives

DC bus undervoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active
Siemens SINAMICS G120F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging
Siemens SINAMICS V90F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off
Siemens MICROMASTER 440F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Allen-Bradley PowerFlex 525F003 Power Loss · F004 UnderVoltage
Delta VFD-ELv Low voltage · dEb Deceleration energy backup error
Delta C2000LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error
Delta ASDA-B2AL003 Under voltage
Hitachi WJ200E09 Under-voltage error
Schneider Electric Altivar ATV320USF Supply mains undervoltage error
INVT Goodrive20 (GD20)UV Bus undervoltage · PoFF System power off
Yaskawa V1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa A1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa GA500Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage
Siemens MICROMASTER 420F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Siemens MICROMASTER 430F0003 Undervoltage · A0503 Undervoltage limit value
Siemens SINAMICS G110F0003 Undervoltage · A0503 Undervoltage limit
INVT Goodrive200A (GD200A)UV Bus undervoltage · PoFF System power failure
Mitsubishi Electric FR-D700UV Undervoltage
Danfoss VLT Micro Drive FC 51Alarm 8 DC under voltage

07 / More codes

Other ACS355 codes

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.