F0016 on the ABB ACS355 is the “EARTH FAULT” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.
The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.
- Code
- F0016
- Type
- Fault (stops the drive)
- Drive
- ABB ACS355
- Kind of fault
- Earth fault
01 / Causes
What causes F0016
- The drive detected an earth (ground) fault in the motor or the motor cable.
- An internal short circuit in the drive can also show as an earth fault.
02 / Checks
What to check for F0016
In the order ABB gives them.
- 01Check the motor.
- 02Check the motor cable, and that its length is within ABB's maximum for the drive.
- 03If fault F0001 appears after the earth fault protection is turned off, the drive has an internal short circuit and needs replacing.
Also in the manual
- Over a fieldbus, the drive reports this fault as code 2330.
- ABB lists this as a programmable fault function: parameters 3017 decide whether the condition is reported and how the drive reacts.
- ABB warns that turning off earth fault protection may damage the drive.
03 / Clearing it
How to clear F0016
- Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
- If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
- Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.
Clear it once. If F0016 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How earth fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
- 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
- 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
- 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
- 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.
05 / Repair
When F0016 means a repair
When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.
If F0016 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Earth fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F30021 Ground fault |
| Siemens SINAMICS V90 | F30021 Ground fault |
| Siemens MICROMASTER 440 | F0021 Ground fault |
| Allen-Bradley PowerFlex 525 | F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd |
| Delta VFD-E | GFF Ground fault |
| Delta C2000 | GFF Ground fault |
| Hitachi WJ200 | E14 Ground fault |
| Schneider Electric Altivar ATV320 | SCF3 Ground short circuit error |
| INVT Goodrive20 (GD20) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Yaskawa V1000 | GF Ground Fault |
| Yaskawa A1000 | GF Ground Fault |
| Yaskawa GA500 | GF Ground Fault |
| Siemens MICROMASTER 430 | F0021 Ground fault |
| INVT Goodrive200A (GD200A) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Mitsubishi Electric FR-D700 | E.GF Output side earth (ground) fault overcurrent at start |
| Danfoss VLT Micro Drive FC 51 | Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2 |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007