PowerFlex 525 F006: Motor Stalled

F006 on the Allen-Bradley PowerFlex 525 is the “Motor Stalled” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.

Code
F006
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Motor stall

01 / Causes

What causes F006

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing motor stall faults explains where it usually comes from.

02 / Checks

What to check for F006

In the order Rockwell Automation gives them.

  1. 01Increase the acceleration time (P041, A442, A444, A446) or reduce the load, so the output current does not stay above the current limit (A484, A485) for too long.
  2. 02Check for an overhauling load.

03 / Clearing it

How to clear F006

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F006 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor stall faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the load turns freely and nothing is jammed.
  2. 02Lengthen the acceleration time and check the current limit setting.
  3. 03Check motor connections (star or delta) against the rating plate and the drive's motor data.

05 / Repair

When F006 means a repair

A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.

If F006 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Motor stall: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation
Siemens SINAMICS V90F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit
Siemens MICROMASTER 440F0453 Motor stalled
ABB ACS355F0012 MOTOR STALL · A2012 MOTOR STALL
Delta C2000oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock
Delta ASDA-B2AL009 Excessive deviation of position command
Schneider Electric Altivar ATV320ANF Load slipping error · SSF Torque limitation error
INVT Goodrive20 (GD20)dEu Speed deviation fault
Yaskawa V1000STo Motor Pull Out or Step Out Detection
Yaskawa A1000LSo LSo Fault · STo Pull-Out Detection
Yaskawa GA500LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected
Mitsubishi Electric FR-D700E.OLT Stall prevention stop
Danfoss VLT Micro Drive FC 51Warning 12 Torque limit

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.