AL003 on the Delta ASDA-B2 is the “Under voltage” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- AL003
- Type
- Alarm (stops the drive)
- Drive
- Delta ASDA-B2
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes AL003
- The main circuit input voltage is below the rated allowable voltage.
- No power supply to the main circuit.
- The wrong power supply for the drive.
02 / Checks
What to check for AL003
In the order Delta Electronics gives them.
- 01Check the main circuit input voltage wiring.
- 02Measure the main circuit voltage with a voltmeter, and check the power switch.
- 03Check with a voltmeter that the power system matches the drive's specification, and use the correct supply.
Also in the manual
- The main circuit voltage is lower than the standard voltage. WARN output; servo off.
- Clears after a power cycle; set P2-66 bit 2 for it to clear by itself once the voltage is back to normal.
03 / Clearing it
How to clear AL003
- Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
- Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
- AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
- AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.
Clear it once. If AL003 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When AL003 means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If AL003 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Siemens MICROMASTER 440 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| ABB ACS355 | F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta C2000 | LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa V1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 420 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other ASDA-B2 codes
Source
Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.