MachineryFix

Delta AC drive (VFD) · fault code

C2000 ocA: Over-current during acceleration

ocA on the Delta C2000 is the “Over-current during acceleration” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.

Code
ocA
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Overcurrent

01 / Causes

What causes ocA

  • The acceleration time is too short.
  • A short circuit at the motor output from poorly insulated wiring.
  • Burnt-out or aged motor insulation.
  • The load is too large, or changes suddenly.
  • A special motor, or a motor larger than the drive.
  • A contactor switching at the drive's output.
  • A V/F curve setting error, or torque compensation set too large.
  • Interference.
  • The motor was started while still coasting, or speed tracking is set wrongly.
  • The control mode does not match the motor.
  • The motor cable is too long.
  • A short circuit or ground fault inside the drive's output stage.
  • Stall prevention set wrongly.

02 / Checks

What to check for ocA

In the order Delta Electronics gives them.

  1. 01Lengthen the acceleration time and the S-curve acceleration time. Auto-acceleration and deceleration (Pr. 01-44) and over-current stall prevention (Pr. 06-03) also help; otherwise fit a larger drive.
  2. 02Check the motor cable for short circuits, and repair or replace it before switching on.
  3. 03Megger the motor and replace it if the insulation is poor.
  4. 04Check whether the output current over the whole working cycle goes above the drive's rated current. If it does, or the load changes suddenly, reduce the load or fit a larger drive.
  5. 05Check the motor's nameplate rated current is no more than the drive's rated current.
  6. 06Check the timing of any contactor on the drive's output (U/V/W): it must not switch on or off while the drive is putting out voltage.
  7. 07Adjust the V/F curve; if the voltage at the fault frequency is too high, lower it.
  8. 08Lower the torque compensation gain (Pr. 07-26) until the output current drops and the motor does not stall.
  9. 09Check the control-circuit wiring and the main-circuit wiring and grounding, to keep interference out.
  10. 10Turn on speed tracking at start-up (Pr. 07-12), and adjust its maximum current (Pr. 07-09).
  11. 11Check the control mode in Pr. 00-11: 0, 1, 2, 3 or 5 for an induction motor; 4, 6 or 7 for a permanent magnet motor.
  12. 12For a long motor cable, fit a larger drive or add an AC reactor on the output (U/V/W).
  13. 13ocA can come from a short circuit or ground fault on the drive's output side. With a meter, check for shorts between the DC terminals (B1, DC-) and U, V, W. If there is a short, Delta's instruction is to return the drive to the factory for repair.
  14. 14Set stall prevention to a suitable value.

Also in the manual

  • Fault ID 1. Trips at 240% of the drive's rated current, immediately. Reset manually, 5 seconds after the fault has cleared.

03 / Clearing it

How to clear ocA

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If ocA comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How overcurrent faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
  2. 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
  3. 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
  4. 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
  5. 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.

05 / Repair

When ocA means a repair

If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.

If ocA keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Overcurrent: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F1 Overcurrent · A501 Current limit
Siemens SINAMICS G120F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active
Siemens SINAMICS V90F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U
Siemens MICROMASTER 440F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value
Allen-Bradley PowerFlex 525F012 HW OverCurrent · F063 SW OverCurrent
ABB ACS355F0001 OVERCURRENT · A2001 OVERCURRENT
Delta VFD-Eoc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed
Delta ASDA-B2AL001 Over current
Hitachi WJ200E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions
Schneider Electric Altivar ATV320OCF Overcurrent error
INVT Goodrive20 (GD20)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Yaskawa V1000oC Overcurrent · HCA Current Alarm
Yaskawa A1000oC Overcurrent · HCA Current Alarm
Yaskawa GA500oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm
Siemens MICROMASTER 420F0001 Overcurrent · A0501 Current limit value
Siemens MICROMASTER 430F0001 Overcurrent · A0501 Current limit value
Siemens SINAMICS G110F0001 Overcurrent · A0501 Current limit
INVT Goodrive200A (GD200A)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Mitsubishi Electric FR-D700E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent)
Danfoss VLT Micro Drive FC 51Alarm 13 Over current · Warning 59 Current limit

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

ocA won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.