ovn on the Delta C2000 is the “Over-voltage at constant speed” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.
- Code
- ovn
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- DC bus overvoltage
01 / Causes
What causes ovn
- A sudden change in load.
- The stall prevention level is set below the no-load current.
- Regenerated energy from the motor's inertia.
- The supply voltage is too high.
- Power-factor capacitors or an active power unit switching on the same supply.
- A ground fault on the motor side.
- Brake resistor or brake unit wired wrongly.
- Interference.
02 / Checks
What to check for ovn
In the order Delta Electronics gives them.
- 01Connect a brake resistor, brake unit or common DC bus; reduce the load; adjust the braking level (Pr. 07-01 or the brake unit's setting); or fit a larger drive.
- 02Set the stall prevention level above the no-load current.
- 03Use over-voltage stall prevention (Pr. 06-01), or a brake unit or common DC bus.
- 04Check the input voltage is within the drive's rated input range, and look for voltage spikes.
- 05If a power-factor capacitor or an active power supply unit switches on the same supply, the input voltage can surge for a moment: install an AC reactor.
- 06Check the motor cable, terminal box and its terminals for a ground fault: ground fault current charges the main-circuit capacitors through the supply.
- 07Check the wiring of the brake resistor or brake unit.
- 08Check the control-circuit wiring and the main-circuit wiring and grounding, to keep interference out.
Also in the manual
- Fault ID 9. The drive closes its output at once and the motor coasts. Trips at a DC bus of 410 V DC (230 V series), 820 V DC (460 V), 1116 V DC (575 V) or 1318 V DC (690 V). Resets only once the DC bus is below 90% of that level.
03 / Clearing it
How to clear ovn
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If ovn comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus overvoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
- 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
- 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
- 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.
05 / Repair
When ovn means a repair
If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.
If ovn keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
DC bus overvoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active |
| Siemens SINAMICS G120 | F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage |
| Siemens SINAMICS V90 | F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage |
| Siemens MICROMASTER 440 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Allen-Bradley PowerFlex 525 | F005 OverVoltage |
| ABB ACS355 | F0002 DC OVERVOLT · A2002 OVERVOLTAGE |
| Delta VFD-E | ov Over-voltage |
| Delta ASDA-B2 | AL002 Over voltage |
| Hitachi WJ200 | E07 Over-voltage protection · E15 Input over-voltage |
| Schneider Electric Altivar ATV320 | OBF DC bus overvoltage error · OSF Supply mains overvoltage error |
| INVT Goodrive20 (GD20) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Yaskawa V1000 | ov Overvoltage |
| Yaskawa A1000 | ov Overvoltage |
| Yaskawa GA500 | ov Overvoltage |
| Siemens MICROMASTER 420 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens MICROMASTER 430 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens SINAMICS G110 | F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active |
| INVT Goodrive200A (GD200A) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Mitsubishi Electric FR-D700 | E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage) |
| Danfoss VLT Micro Drive FC 51 | Alarm 7 DC overvoltage |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007