MachineryFix

Delta AC drive (VFD) · fault code

C2000 GFF: Ground fault

GFF on the Delta C2000 is the “Ground fault” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
GFF
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Earth fault

01 / Causes

What causes GFF

  • Burnt-out or aged motor insulation.
  • A short circuit from a broken cable.
  • High stray capacitance in the cable and terminals.
  • Interference.
  • A hardware failure.

02 / Checks

What to check for GFF

In the order Delta Electronics gives them.

  1. 01Megger the motor and replace it if the insulation is poor.
  2. 02Find and clear the short circuit, and replace the cable.
  3. 03If the motor cable is longer than 100 m, lower the carrier frequency, and take steps to reduce stray capacitance.
  4. 04Check the communication wiring and its grounding. Delta recommends running the communication cable apart from the main circuit, or crossing it at 90 degrees.
  5. 05Check the motor, the cable and its length, then switch the power off and on. If it is still there, Delta's instruction is to return the drive to the factory for repair.

Also in the manual

  • Fault ID 4. Trips when an output terminal is grounded and the short-circuit current stays above Pr. 06-60 (default 60%) for longer than Pr. 06-61. Reset manually, 5 seconds after the fault has cleared.
  • Delta notes that this protection is there to protect the drive, not people.

03 / Clearing it

How to clear GFF

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If GFF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When GFF means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If GFF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30021 Ground fault
Siemens SINAMICS V90F30021 Ground fault
Siemens MICROMASTER 440F0021 Ground fault
Allen-Bradley PowerFlex 525F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
INVT Goodrive20 (GD20)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Yaskawa V1000GF Ground Fault
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

GFF won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.