C2000 OPHL: Output phase loss

OPHL on the Delta C2000 is the “Output phase loss” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.

Code
OPHL
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Output phase loss

01 / Causes

What causes OPHL

  • Unbalanced three-phase impedance in the motor.
  • The motor is wired wrongly.
  • A single-phase motor is used.
  • The current sensor is damaged.
  • The drive is much larger than the motor.

02 / Checks

What to check for OPHL

In the order Delta Electronics gives them.

  1. 01Replace the motor.
  2. 02Check the cable and replace it if needed.
  3. 03Use a three-phase motor.
  4. 04Check the control board's flat cable; if it is loose, reconnect it and test again. If the fault stays, Delta's instruction is to return the drive to the factory.
  5. 05Check the three output currents are balanced with a clamp meter. If they are balanced and OPHL stays, Delta's instruction is to return the drive to the factory.
  6. 06Match the drive to the motor's size.

Also in the manual

  • Fault IDs 82, 83 and 84, for a loss on the U, V or W phase. Detection level Pr. 06-47, time Pr. 06-46 (Pr. 06-48 when DC braking is used).
  • Pr. 06-45 sets the response: 1 or 2 makes it a fault that is recorded; 0 warns and keeps running; 3 gives no warning.

03 / Clearing it

How to clear OPHL

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If OPHL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
  2. 02Inspect any contactor, isolator or junction box in the motor circuit.
  3. 03Measure winding resistance phase to phase at the motor.

05 / Repair

When OPHL means a repair

When cable, connections and windings are all good, an output phase in the drive itself may be open.

If OPHL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Output phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A922 No load applied to inverter
Siemens SINAMICS G120F30015 Motor cable phase failure
Siemens SINAMICS V90F7410 Current controller output limited · F30015 Phase failure motor cable
Siemens MICROMASTER 440F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter
Allen-Bradley PowerFlex 525F021 Output Ph Loss
ABB ACS355F0034 MOTOR PHASE
Delta ASDA-B2AL031 Incorrect wiring of the motor power line U, V, W, GND
Schneider Electric Altivar ATV320OPF1 Single output phase loss error · OPF2 Output phase loss error
INVT Goodrive20 (GD20)SPO Phase loss on output side
Yaskawa V1000LF Output Phase Loss · LF2 Output current imbalance
Yaskawa A1000LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance
Yaskawa GA500LF Output Phase Loss · LF2 Output Current Imbalance
Siemens MICROMASTER 430F0023 Output fault · A0523 Output fault
INVT Goodrive200A (GD200A)SPO Phase loss on output side
Mitsubishi Electric FR-D700E.LF Output phase loss
Danfoss VLT Micro Drive FC 51Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OPHL won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.