Altivar ATV320 OPF2: Output phase loss error

OPF2 on the Schneider Electric Altivar ATV320 is the “Output phase loss error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.

Code
OPF2
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Output phase loss

01 / Causes

What causes OPF2

  • The motor is not connected, or its power is too low.
  • An output contactor is open.
  • A momentary instability in the motor current.

02 / Checks

What to check for OPF2

In the order Schneider Electric gives them.

  1. 01Check the connections from the drive to the motor.
  2. 02If an output contactor is used, set output phase loss (OPL) to No Error Triggered (OAC).
  3. 03To test the drive on a small motor or with no motor, turn output phase loss detection off (OPL = No); it is on in the factory settings.
  4. 04Check and optimise IR compensation (UFR), nominal motor voltage (UNS) and nominal motor current (NCR), and run autotuning (TUN).

Also in the manual

  • Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.

03 / Clearing it

How to clear OPF2

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If OPF2 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
  2. 02Inspect any contactor, isolator or junction box in the motor circuit.
  3. 03Measure winding resistance phase to phase at the motor.

05 / Repair

When OPF2 means a repair

When cable, connections and windings are all good, an output phase in the drive itself may be open.

If OPF2 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Output phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A922 No load applied to inverter
Siemens SINAMICS G120F30015 Motor cable phase failure
Siemens SINAMICS V90F7410 Current controller output limited · F30015 Phase failure motor cable
Siemens MICROMASTER 440F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter
Allen-Bradley PowerFlex 525F021 Output Ph Loss
ABB ACS355F0034 MOTOR PHASE
Delta C2000OPHL Output phase loss
Delta ASDA-B2AL031 Incorrect wiring of the motor power line U, V, W, GND
INVT Goodrive20 (GD20)SPO Phase loss on output side
Yaskawa V1000LF Output Phase Loss · LF2 Output current imbalance
Yaskawa A1000LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance
Yaskawa GA500LF Output Phase Loss · LF2 Output Current Imbalance
Siemens MICROMASTER 430F0023 Output fault · A0523 Output fault
INVT Goodrive200A (GD200A)SPO Phase loss on output side
Mitsubishi Electric FR-D700E.LF Output phase loss
Danfoss VLT Micro Drive FC 51Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OPF2 won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.