PowerFlex 525 F021: Output Ph Loss

F021 on the Allen-Bradley PowerFlex 525 is the “Output Ph Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.

Code
F021
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Output phase loss

01 / Causes

What causes F021

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing output phase loss faults explains where it usually comes from.

02 / Checks

What to check for F021

In the order Rockwell Automation gives them.

  1. 01Check the motor wiring.
  2. 02Check the motor.

Also in the manual

  • Output phase loss detection is turned on or off with A557 [Out Phas Loss En].

03 / Clearing it

How to clear F021

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F021 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
  2. 02Inspect any contactor, isolator or junction box in the motor circuit.
  3. 03Measure winding resistance phase to phase at the motor.

05 / Repair

When F021 means a repair

When cable, connections and windings are all good, an output phase in the drive itself may be open.

If F021 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Output phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20A922 No load applied to inverter
Siemens SINAMICS G120F30015 Motor cable phase failure
Siemens SINAMICS V90F7410 Current controller output limited · F30015 Phase failure motor cable
Siemens MICROMASTER 440F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter
ABB ACS355F0034 MOTOR PHASE
Delta C2000OPHL Output phase loss
Delta ASDA-B2AL031 Incorrect wiring of the motor power line U, V, W, GND
Schneider Electric Altivar ATV320OPF1 Single output phase loss error · OPF2 Output phase loss error
INVT Goodrive20 (GD20)SPO Phase loss on output side
Yaskawa V1000LF Output Phase Loss · LF2 Output current imbalance
Yaskawa A1000LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance
Yaskawa GA500LF Output Phase Loss · LF2 Output Current Imbalance
Siemens MICROMASTER 430F0023 Output fault · A0523 Output fault
INVT Goodrive200A (GD200A)SPO Phase loss on output side
Mitsubishi Electric FR-D700E.LF Output phase loss
Danfoss VLT Micro Drive FC 51Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F021 won't clear? Get a technician who knows the PowerFlex 525.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.