F021 on the Allen-Bradley PowerFlex 525 is the “Output Ph Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.
- Code
- F021
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Output phase loss
01 / Causes
What causes F021
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing output phase loss faults explains where it usually comes from.
02 / Checks
What to check for F021
In the order Rockwell Automation gives them.
- 01Check the motor wiring.
- 02Check the motor.
Also in the manual
- Output phase loss detection is turned on or off with A557 [Out Phas Loss En].
03 / Clearing it
How to clear F021
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F021 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
- 02Inspect any contactor, isolator or junction box in the motor circuit.
- 03Measure winding resistance phase to phase at the motor.
05 / Repair
When F021 means a repair
When cable, connections and windings are all good, an output phase in the drive itself may be open.
If F021 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Output phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A922 No load applied to inverter |
| Siemens SINAMICS G120 | F30015 Motor cable phase failure |
| Siemens SINAMICS V90 | F7410 Current controller output limited · F30015 Phase failure motor cable |
| Siemens MICROMASTER 440 | F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter |
| ABB ACS355 | F0034 MOTOR PHASE |
| Delta C2000 | OPHL Output phase loss |
| Delta ASDA-B2 | AL031 Incorrect wiring of the motor power line U, V, W, GND |
| Schneider Electric Altivar ATV320 | OPF1 Single output phase loss error · OPF2 Output phase loss error |
| INVT Goodrive20 (GD20) | SPO Phase loss on output side |
| Yaskawa V1000 | LF Output Phase Loss · LF2 Output current imbalance |
| Yaskawa A1000 | LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance |
| Yaskawa GA500 | LF Output Phase Loss · LF2 Output Current Imbalance |
| Siemens MICROMASTER 430 | F0023 Output fault · A0523 Output fault |
| INVT Goodrive200A (GD200A) | SPO Phase loss on output side |
| Mitsubishi Electric FR-D700 | E.LF Output phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.