F30015 on the Siemens SINAMICS G120 is the “Motor cable phase failure” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The drive sees current in only two of the three motor phases. A phase is open somewhere between the drive and the motor winding.
- Code
- F30015
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Output phase loss
01 / Causes
What causes F30015
Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing output phase loss faults explains where it usually comes from.
02 / Checks
What to check for F30015
In the order Siemens gives them.
- 01Check the motor cables.
- 02Lengthen the ramp-up or ramp-down time (p1120).
03 / Clearing it
How to clear F30015
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F30015 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and check continuity of each phase from the drive terminals to the motor terminals.
- 02Inspect any contactor, isolator or junction box in the motor circuit.
- 03Measure winding resistance phase to phase at the motor.
05 / Repair
When F30015 means a repair
When cable, connections and windings are all good, an output phase in the drive itself may be open.
If F30015 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Output phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | A922 No load applied to inverter |
| Siemens SINAMICS V90 | F7410 Current controller output limited · F30015 Phase failure motor cable |
| Siemens MICROMASTER 440 | F0023 Output fault · F0422 No load applied to inverter · A0523 Output fault · A0922 No load at the inverter |
| Allen-Bradley PowerFlex 525 | F021 Output Ph Loss |
| ABB ACS355 | F0034 MOTOR PHASE |
| Delta C2000 | OPHL Output phase loss |
| Delta ASDA-B2 | AL031 Incorrect wiring of the motor power line U, V, W, GND |
| Schneider Electric Altivar ATV320 | OPF1 Single output phase loss error · OPF2 Output phase loss error |
| INVT Goodrive20 (GD20) | SPO Phase loss on output side |
| Yaskawa V1000 | LF Output Phase Loss · LF2 Output current imbalance |
| Yaskawa A1000 | LF Output Phase Loss · LF2 Output Current Imbalance · LF3 Power Unit Output Phase Loss 3 · UnbC Current Unbalance |
| Yaskawa GA500 | LF Output Phase Loss · LF2 Output Current Imbalance |
| Siemens MICROMASTER 430 | F0023 Output fault · A0523 Output fault |
| INVT Goodrive200A (GD200A) | SPO Phase loss on output side |
| Mitsubishi Electric FR-D700 | E.LF Output phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 30 Motor phase U missing · Alarm 31 Motor phase V missing · Alarm 32 Motor phase W missing |