oH3 on the Delta C2000 is the “Motor overheating” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.
- Code
- oH3
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Motor overload or overtemperature
01 / Causes
What causes oH3
- A locked motor shaft.
- The load is too large.
- The ambient temperature is too high.
- The motor's cooling system or fan has failed.
- The motor runs at low speed for too long.
- The acceleration or deceleration time, or the working cycle, is too short.
- The V/F voltage is too high.
- The motor rated current setting does not match the nameplate.
- The PTC or PT100 is set up or wired wrongly.
- Stall prevention set wrongly.
- Unbalanced three-phase impedance in the motor.
- High harmonics.
02 / Checks
What to check for oH3
In the order Delta Electronics gives them.
- 01Free the locked shaft.
- 02Reduce the load, or use a larger motor.
- 03Move the drive away from heat sources, or add a cooling fan or air conditioning to lower the ambient temperature.
- 04Get the motor's cooling system working; replace a failed fan.
- 05Shorten low-speed running, use a motor made for drive duty, or use a larger motor.
- 06Lengthen the acceleration and deceleration times (Pr. 01-12 to 01-19).
- 07Adjust the V/F curve (Pr. 01-01 to 01-08), especially the mid-point voltage, and see the V/F curve selection in Pr. 01-43. A mid-point voltage set too low reduces the load capacity at low speed.
- 08Set the motor rated current to the nameplate value.
- 09Check the connection between the PTC or PT100 and the protection input.
- 10Set stall prevention to a suitable value.
- 11If the motor's three-phase impedance is unbalanced, replace the motor.
- 12Take steps to reduce harmonics.
Also in the manual
- Fault ID 24. Shown for both motor temperature inputs: a PTC (an analog input set to 6) above Pr. 06-30 (default 50%), or a PT100 (an analog input set to 11) above Pr. 06-57 (default 7 V).
- Pr. 06-29 sets the response: 0 warn and keep running, 1 warn and ramp to stop, 2 warn and coast to stop, 3 no warning. At 1 or 2 it is a fault that is recorded and reset manually; at 0 it is a warning that clears itself.
03 / Clearing it
How to clear oH3
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If oH3 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor overload or overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare running current with the motor's rating plate current.
- 02Check the motor overload settings in the drive against the rating plate.
- 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
- 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.
05 / Repair
When oH3 means a repair
A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.
If oH3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Motor overload or overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F11 Motor overtemperature · A511 Motor overtemperature I2t |
| Siemens SINAMICS G120 | F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature |
| Siemens SINAMICS V90 | F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature |
| Siemens MICROMASTER 440 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Allen-Bradley PowerFlex 525 | F007 Motor Overload |
| ABB ACS355 | F0009 MOT OVERTEMP · A2010 MOTOR TEMP |
| Delta VFD-E | oL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection |
| Delta ASDA-B2 | AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload |
| Hitachi WJ200 | E05 Overload protection · E35 Thermistor |
| Schneider Electric Altivar ATV320 | OLF Motor overload error · OTFL DI6=PTC overheat error |
| INVT Goodrive20 (GD20) | OL1 Motor overload |
| Yaskawa V1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Yaskawa A1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload |
| Yaskawa GA500 | oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Siemens MICROMASTER 420 | F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t |
| Siemens MICROMASTER 430 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Siemens SINAMICS G110 | F0011 Motor over temperature I2t · A0511 Motor over temperature I2t |
| INVT Goodrive200A (GD200A) | OL1 Motor overload |
| Mitsubishi Electric FR-D700 | E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 10 Motor ETR over temperature |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007