C2000 SdRv: Reverse direction of the speed feedback

SdRv on the Delta C2000 is the “Reverse direction of the speed feedback” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.

Code
SdRv
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Motor stall

01 / Causes

What causes SdRv

  • The speed observer bandwidth (Pr. 10-25) is set wrongly.
  • The motor parameters are wrong.
  • The motor cable is faulty or broken.
  • The motor is pushed backwards, or turns in reverse at start.
  • Interference.

02 / Checks

What to check for SdRv

In the order Delta Electronics gives them.

  1. 01Lower Pr. 10-25.
  2. 02Set the motor parameters again and run auto-tuning.
  3. 03Check the cable, or replace it.
  4. 04Turn on speed tracking at start (Pr. 07-12).
  5. 05Check the control-circuit wiring and the main-circuit wiring and grounding, to keep interference out.

Also in the manual

  • Fault ID 68. In sensorless control, the motor turns opposite to the commanded direction. Pr. 10-08 sets the response.

03 / Clearing it

How to clear SdRv

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If SdRv comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor stall faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the load turns freely and nothing is jammed.
  2. 02Lengthen the acceleration time and check the current limit setting.
  3. 03Check motor connections (star or delta) against the rating plate and the drive's motor data.

05 / Repair

When SdRv means a repair

A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.

If SdRv keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Motor stall: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation
Siemens SINAMICS V90F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit
Siemens MICROMASTER 440F0453 Motor stalled
Allen-Bradley PowerFlex 525F006 Motor Stalled
ABB ACS355F0012 MOTOR STALL · A2012 MOTOR STALL
Delta ASDA-B2AL009 Excessive deviation of position command
Schneider Electric Altivar ATV320ANF Load slipping error · SSF Torque limitation error
INVT Goodrive20 (GD20)dEu Speed deviation fault
Yaskawa V1000STo Motor Pull Out or Step Out Detection
Yaskawa A1000LSo LSo Fault · STo Pull-Out Detection
Yaskawa GA500LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected
Mitsubishi Electric FR-D700E.OLT Stall prevention stop
Danfoss VLT Micro Drive FC 51Warning 12 Torque limit

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SdRv won't clear? Get a technician who knows the C2000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.