MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 LSo: Low Speed Motor Step-Out

LSo on the Yaskawa GA500 is the “Low Speed Motor Step-Out” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.

Code
LSo
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Motor stall

01 / Causes

What causes LSo

  • The motor code is set wrongly, the load is too large, or an external force turned the motor at start.
  • The drive detected the magnetic pole position wrongly, n8-84 (Polarity Detection Current) is too low, or L8-93 to L8-95 are set wrongly.

02 / Checks

What to check for LSo

In the order Yaskawa gives them.

  1. 01Set E5-01 (PM Motor Code Selection) for the motor; for special motors, set the E5 parameters from the motor test report.
  2. 02Reduce the load, or fit a larger drive and motor.
  3. 03Fix load-side problems that turn the motor at start.
  4. 04Set b3-01 = 1; if U6-57 is below 819, raise n8-84 (check the motor maker's limits).
  5. 05Raise L8-93 to L8-95, and with an IPM motor do High Frequency Injection Auto-Tuning.

Also in the manual

  • Detected on step-out at low speed. It stops the motor and a reverse run when a motor without a motor code misreads its initial polarity.

03 / Clearing it

How to clear LSo

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If LSo comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor stall faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the load turns freely and nothing is jammed.
  2. 02Lengthen the acceleration time and check the current limit setting.
  3. 03Check motor connections (star or delta) against the rating plate and the drive's motor data.

05 / Repair

When LSo means a repair

A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.

If LSo keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor stall: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation
Siemens SINAMICS V90F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit
Siemens MICROMASTER 440F0453 Motor stalled
Allen-Bradley PowerFlex 525F006 Motor Stalled
ABB ACS355F0012 MOTOR STALL · A2012 MOTOR STALL
Delta C2000oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock
Delta ASDA-B2AL009 Excessive deviation of position command
Schneider Electric Altivar ATV320ANF Load slipping error · SSF Torque limitation error
INVT Goodrive20 (GD20)dEu Speed deviation fault
Yaskawa V1000STo Motor Pull Out or Step Out Detection
Yaskawa A1000LSo LSo Fault · STo Pull-Out Detection
Mitsubishi Electric FR-D700E.OLT Stall prevention stop
Danfoss VLT Micro Drive FC 51Warning 12 Torque limit

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

LSo won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.