F07900 on the Siemens SINAMICS G120 is the “Motor blocked” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- F07900
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Motor stall
01 / Causes
What causes F07900
Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing motor stall faults explains where it usually comes from.
02 / Checks
What to check for F07900
In the order Siemens gives them.
- 01Check the motor can turn freely.
- 02Check the torque limits (r1538 and r1539).
- 03Check the parameters of the "Motor blocked" message (p2175, p2177).
03 / Clearing it
How to clear F07900
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F07900 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When F07900 means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If F07900 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V90 | F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit |
| Siemens MICROMASTER 440 | F0453 Motor stalled |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| INVT Goodrive20 (GD20) | dEu Speed deviation fault |
| Yaskawa V1000 | STo Motor Pull Out or Step Out Detection |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Yaskawa GA500 | LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |
07 / More codes
Other SINAMICS G120 codes
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007