F7450 on the Siemens SINAMICS V90 is the “Standstill monitoring has responded” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- F7450
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Kind of fault
- Motor stall
01 / Causes
What causes F7450
- The position loop gain is too low, or too high (instability or oscillation).
- A mechanical overload.
- The cable between motor and drive is wrong (a phase missing or swapped).
02 / Checks
What to check for F7450
In the order Siemens gives them.
- 01Check these causes and fix them.
Also in the manual
- Reaction OFF1: the motor ramps down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
- After the standstill monitoring time expired, the drive left the standstill window.
03 / Clearing it
How to clear F7450
- Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
- Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
- If the cause is not removed, the fault can come back after five seconds with no button pressed.
- Alarms acknowledge themselves.
Clear it once. If F7450 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When F7450 means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If F7450 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation |
| Siemens MICROMASTER 440 | F0453 Motor stalled |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| INVT Goodrive20 (GD20) | dEu Speed deviation fault |
| Yaskawa V1000 | STo Motor Pull Out or Step Out Detection |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Yaskawa GA500 | LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |
07 / More codes
Other SINAMICS V90 codes
Source
Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007