MachineryFix

Siemens AC drive (VFD) · alarm code

SINAMICS G120 A07903: Motor speed deviation

A07903 on the Siemens SINAMICS G120 is the “Motor speed deviation” alarm. An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.

The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.

Code
A07903
Type
Alarm (warning)
Drive
Siemens SINAMICS G120, CU240B-2, CU240E-2
Kind of fault
Motor stall

01 / Causes

What causes A07903

Siemens's table names this alarm and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing motor stall faults explains where it usually comes from.

02 / Checks

What to check for A07903

In the order Siemens gives them.

  1. 01Increase p2163 and/or p2166.
  2. 02Increase the torque, current and power limits.

03 / Clearing it

How to clear A07903

An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.

If A07903 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How motor stall faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the load turns freely and nothing is jammed.
  2. 02Lengthen the acceleration time and check the current limit setting.
  3. 03Check motor connections (star or delta) against the rating plate and the drive's motor data.

05 / Repair

When A07903 means a repair

A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.

If A07903 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Motor stall: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit
Siemens MICROMASTER 440F0453 Motor stalled
Allen-Bradley PowerFlex 525F006 Motor Stalled
ABB ACS355F0012 MOTOR STALL · A2012 MOTOR STALL
Delta C2000oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock
Delta ASDA-B2AL009 Excessive deviation of position command
Schneider Electric Altivar ATV320ANF Load slipping error · SSF Torque limitation error
INVT Goodrive20 (GD20)dEu Speed deviation fault
Yaskawa V1000STo Motor Pull Out or Step Out Detection
Yaskawa A1000LSo LSo Fault · STo Pull-Out Detection
Yaskawa GA500LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected
Mitsubishi Electric FR-D700E.OLT Stall prevention stop
Danfoss VLT Micro Drive FC 51Warning 12 Torque limit

07 / More codes

Other SINAMICS G120 codes

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

A07903 won't clear? Get a technician who knows the SINAMICS G120.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.