Altivar ATV320 SSF: Torque limitation error

SSF on the Schneider Electric Altivar ATV320 is the “Torque limitation error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.

Code
SSF
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Motor stall

01 / Causes

What causes SSF

  • The drive switched to torque or current limitation.

02 / Checks

What to check for SSF

In the order Schneider Electric gives them.

  1. 01Check for mechanical problems.
  2. 02Check the torque limitation (TOL-) and torque or current limit detection (TID-) parameters.

Also in the manual

  • Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.

03 / Clearing it

How to clear SSF

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If SSF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor stall faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the load turns freely and nothing is jammed.
  2. 02Lengthen the acceleration time and check the current limit setting.
  3. 03Check motor connections (star or delta) against the rating plate and the drive's motor data.

05 / Repair

When SSF means a repair

A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.

If SSF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Motor stall: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation
Siemens SINAMICS V90F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit
Siemens MICROMASTER 440F0453 Motor stalled
Allen-Bradley PowerFlex 525F006 Motor Stalled
ABB ACS355F0012 MOTOR STALL · A2012 MOTOR STALL
Delta C2000oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock
Delta ASDA-B2AL009 Excessive deviation of position command
INVT Goodrive20 (GD20)dEu Speed deviation fault
Yaskawa V1000STo Motor Pull Out or Step Out Detection
Yaskawa A1000LSo LSo Fault · STo Pull-Out Detection
Yaskawa GA500LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected
Mitsubishi Electric FR-D700E.OLT Stall prevention stop
Danfoss VLT Micro Drive FC 51Warning 12 Torque limit

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.