PHF on the Schneider Electric Altivar ATV320 is the “Input phase loss error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.
- Code
- PHF
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- Input phase loss
01 / Causes
What causes PHF
- The drive is supplied wrongly, or a fuse has blown.
- One phase is missing.
- A three-phase ATV320 is on a single-phase supply.
- An unbalanced load.
02 / Checks
What to check for PHF
In the order Schneider Electric gives them.
- 01Check the power connection and the fuses.
- 02Use a three-phase supply.
- 03The error can be switched off with input phase loss assignment (IPL) = No.
Also in the manual
- Clears by itself as soon as the cause is gone.
- This protection works only with the drive on load.
03 / Clearing it
How to clear PHF
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If PHF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How input phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure all three phases at the drive input terminals with the drive running under load.
- 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
- 03Tighten and inspect supply terminals for heat damage.
05 / Repair
When PHF means a repair
If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.
If PHF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
Input phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F20 DC ripple too high |
| Siemens SINAMICS G120 | F30011 Line phase failure |
| Siemens SINAMICS V90 | F30011 Line phase failure in main circuit |
| Siemens MICROMASTER 440 | F0020 Line supply phase missing |
| ABB ACS355 | F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS |
| Delta VFD-E | PHL Phase loss |
| Delta C2000 | OrP Phase loss protection |
| Delta ASDA-B2 | AL022 Main circuit power lack phase |
| INVT Goodrive20 (GD20) | SPI Phase loss on input side |
| Yaskawa V1000 | PF Input Phase Loss |
| Yaskawa A1000 | PF Input Phase Loss |
| Yaskawa GA500 | PF Input Phase Loss |
| Siemens MICROMASTER 430 | F0020 Line supply phase missing |
| INVT Goodrive200A (GD200A) | SPI Phase loss on input side |
| Mitsubishi Electric FR-D700 | E.ILF Input phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 4 Mains phase loss |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.