MachineryFix

Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 TJF: IGBT overheating

TJF on the Schneider Electric Altivar ATV320 is the “IGBT overheating” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.

Code
TJF
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Drive overtemperature

01 / Causes

What causes TJF

  • The drive overheated.

02 / Checks

What to check for TJF

In the order Schneider Electric gives them.

  1. 01Check the load, motor and drive are sized to each other.
  2. 02Lower the switching frequency.
  3. 03Let it cool before restarting.

Also in the manual

  • Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.

03 / Clearing it

How to clear TJF

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If TJF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
  2. 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
  3. 03Measure the temperature inside the panel and check the panel fans and filters.
  4. 04Check the switching frequency against the factory setting and the load current against the drive's rating.

05 / Repair

When TJF means a repair

A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.

If TJF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Drive overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning
Siemens SINAMICS G120F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature
Siemens SINAMICS V90F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature
Siemens MICROMASTER 440F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high
Allen-Bradley PowerFlex 525F008 Heatsink OvrTmp · F009 CC OvrTmp
ABB ACS355F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP
Delta VFD-EoH1 IGBT overheat · oH2 Power board overheat
Delta C2000oH1 IGBT overheating · oH2 Heatsink overheating
Delta ASDA-B2AL016 IGBT overheat
Hitachi WJ200E21 Inverter thermal trip
INVT Goodrive20 (GD20)OH1 Rectifier module overheat · OH2 Inverter module overheat
Yaskawa V1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat)
Yaskawa A1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning
Yaskawa GA500oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B)
Siemens MICROMASTER 420F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens MICROMASTER 430F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens SINAMICS G110F0004 Inverter over temperature
INVT Goodrive200A (GD200A)OH1 Rectifier module overheating · OH2 Inverter module overheat
Mitsubishi Electric FR-D700E.FIN Heatsink overheat
Danfoss VLT Micro Drive FC 51Alarm 29 Heat sink temperature

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

TJF won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.