SINAMICS G120 F03505: Analog input, wire break

F03505 on the Siemens SINAMICS G120 is the “Analog input, wire break” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.

An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.

Code
F03505
Type
Fault (stops the drive)
Drive
Siemens SINAMICS G120, CU240B-2, CU240E-2
Kind of fault
Analog signal loss

01 / Causes

What causes F03505

Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing analog signal loss faults explains where it usually comes from.

02 / Checks

What to check for F03505

In the order Siemens gives them.

  1. 01Check the wiring for breaks.
  2. 02Check the level of the signal fed in.
  3. 03The input current measured by the analog input can be read in r0752.

03 / Clearing it

How to clear F03505

  • Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
  • Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
  • Alarms need no acknowledgement: they disappear once the cause is removed.

Clear it once. If F03505 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How analog signal loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure the signal at the drive terminals while the system runs.
  2. 02Check the wiring back to the source for breaks and loose terminals.
  3. 03Check the transmitter or the PLC's analog output that supplies the signal.

05 / Repair

When F03505 means a repair

If the signal is correct at the terminals, the drive's analog input may have failed.

If F03505 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Analog signal loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F80 Signal lost on analog input
Siemens MICROMASTER 440F0080 ADC input signal lost
Allen-Bradley PowerFlex 525F029 Analog In Loss
ABB ACS355F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS
Delta VFD-EAErr ACI signal error
Delta C2000AFE PID loss ACI · ACE ACI loss
Schneider Electric Altivar ATV320LFF3 AI3 4-20mA loss error
INVT Goodrive20 (GD20)PIDE PID feedback offline fault
Siemens MICROMASTER 420F0080 ADC input signal lost
Siemens MICROMASTER 430F0080 ADC input signal lost
INVT Goodrive200A (GD200A)PIDE PID feedback offline fault
Danfoss VLT Micro Drive FC 51Alarm 2 Live zero error

07 / More codes

Other SINAMICS G120 codes

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F03505 won't clear? Get a technician who knows the SINAMICS G120.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.