F029 on the Allen-Bradley PowerFlex 525 is the “Analog In Loss” fault. A fault stops the drive; it will not restart until the fault is cleared.
An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.
- Code
- F029
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Analog signal loss
01 / Causes
What causes F029
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing analog signal loss faults explains where it usually comes from.
02 / Checks
What to check for F029
In the order Rockwell Automation gives them.
- 01Check for broken or loose connections at the inputs.
- 02Check the parameters.
03 / Clearing it
How to clear F029
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F029 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How analog signal loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure the signal at the drive terminals while the system runs.
- 02Check the wiring back to the source for breaks and loose terminals.
- 03Check the transmitter or the PLC's analog output that supplies the signal.
05 / Repair
When F029 means a repair
If the signal is correct at the terminals, the drive's analog input may have failed.
If F029 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Analog signal loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F80 Signal lost on analog input |
| Siemens SINAMICS G120 | F03505 Analog input, wire break |
| Siemens MICROMASTER 440 | F0080 ADC input signal lost |
| ABB ACS355 | F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS |
| Delta VFD-E | AErr ACI signal error |
| Delta C2000 | AFE PID loss ACI · ACE ACI loss |
| Schneider Electric Altivar ATV320 | LFF3 AI3 4-20mA loss error |
| INVT Goodrive20 (GD20) | PIDE PID feedback offline fault |
| Siemens MICROMASTER 420 | F0080 ADC input signal lost |
| Siemens MICROMASTER 430 | F0080 ADC input signal lost |
| INVT Goodrive200A (GD200A) | PIDE PID feedback offline fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 2 Live zero error |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007