ACS355 A2007: AI2 LOSS

A2007 on the ABB ACS355 is the “AI2 LOSS” alarm. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.

An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.

Code
A2007
Type
Alarm (warning)
Drive
ABB ACS355
Kind of fault
Analog signal loss

01 / Causes

What causes A2007

  • The signal on analog input AI2 fell below the limit set in parameter 3022 AI2 FAULT LIMIT.

02 / Checks

What to check for A2007

In the order ABB gives them.

  1. 01Check the signal source and the wiring of analog input AI2: the signal may be weak or missing.
  2. 02Check parameters 3001 AI<MIN FUNCTION and 3022 AI2 FAULT LIMIT: the signal may simply be below the fault limit set there.

Also in the manual

  • ABB's alarm table refers to fault F0008 for the causes and checks, which are repeated here.
  • ABB lists this as a programmable fault function: parameters 3001 and 3022 decide whether the condition is reported and how the drive reacts.

03 / Clearing it

How to clear A2007

An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.

If A2007 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How analog signal loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure the signal at the drive terminals while the system runs.
  2. 02Check the wiring back to the source for breaks and loose terminals.
  3. 03Check the transmitter or the PLC's analog output that supplies the signal.

05 / Repair

When A2007 means a repair

If the signal is correct at the terminals, the drive's analog input may have failed.

If A2007 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.

06 / Other drives

Analog signal loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F80 Signal lost on analog input
Siemens SINAMICS G120F03505 Analog input, wire break
Siemens MICROMASTER 440F0080 ADC input signal lost
Allen-Bradley PowerFlex 525F029 Analog In Loss
Delta VFD-EAErr ACI signal error
Delta C2000AFE PID loss ACI · ACE ACI loss
Schneider Electric Altivar ATV320LFF3 AI3 4-20mA loss error
INVT Goodrive20 (GD20)PIDE PID feedback offline fault
Siemens MICROMASTER 420F0080 ADC input signal lost
Siemens MICROMASTER 430F0080 ADC input signal lost
INVT Goodrive200A (GD200A)PIDE PID feedback offline fault
Danfoss VLT Micro Drive FC 51Alarm 2 Live zero error

07 / More codes

Other ACS355 codes

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.