A2006 on the ABB ACS355 is the “AI1 LOSS” alarm. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.
- Code
- A2006
- Type
- Alarm (warning)
- Drive
- ABB ACS355
- Kind of fault
- Analog signal loss
01 / Causes
What causes A2006
- The signal on analog input AI1 fell below the limit set in parameter 3021 AI1 FAULT LIMIT.
02 / Checks
What to check for A2006
In the order ABB gives them.
- 01Check the signal source and the wiring of analog input AI1: the signal may be weak or missing.
- 02Check parameters 3001 AI<MIN FUNCTION and 3021 AI1 FAULT LIMIT: the signal may simply be below the fault limit set there.
Also in the manual
- ABB's alarm table refers to fault F0007 for the causes and checks, which are repeated here.
- ABB lists this as a programmable fault function: parameters 3001 and 3021 decide whether the condition is reported and how the drive reacts.
03 / Clearing it
How to clear A2006
An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
If A2006 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How analog signal loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure the signal at the drive terminals while the system runs.
- 02Check the wiring back to the source for breaks and loose terminals.
- 03Check the transmitter or the PLC's analog output that supplies the signal.
05 / Repair
When A2006 means a repair
If the signal is correct at the terminals, the drive's analog input may have failed.
If A2006 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Analog signal loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F80 Signal lost on analog input |
| Siemens SINAMICS G120 | F03505 Analog input, wire break |
| Siemens MICROMASTER 440 | F0080 ADC input signal lost |
| Allen-Bradley PowerFlex 525 | F029 Analog In Loss |
| Delta VFD-E | AErr ACI signal error |
| Delta C2000 | AFE PID loss ACI · ACE ACI loss |
| Schneider Electric Altivar ATV320 | LFF3 AI3 4-20mA loss error |
| INVT Goodrive20 (GD20) | PIDE PID feedback offline fault |
| Siemens MICROMASTER 420 | F0080 ADC input signal lost |
| Siemens MICROMASTER 430 | F0080 ADC input signal lost |
| INVT Goodrive200A (GD200A) | PIDE PID feedback offline fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 2 Live zero error |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007