F30001 on the Siemens SINAMICS V90 is the “Power unit: Overcurrent” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.
The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.
- Code
- F30001
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Kind of fault
- Overcurrent
01 / Causes
What causes F30001
- Closed-loop control is set up wrongly, or the controller settings are not suitable.
- A short circuit or ground fault in the motor.
- The power cables are not connected correctly, or are longer than allowed.
- The power unit is defective.
- A line phase is interrupted.
02 / Checks
What to check for F30001
In the order Siemens gives them.
- 01Check the motor data, and commission again if needed.
- 02Adjust the speed loop gain Kp (p29120) and the position loop gain Kv (p29110).
- 03Check the motor's star or delta connection.
- 04Check the power cable connections, and the power cables for a short circuit or ground fault.
- 05Check the length of the power cables.
- 06Replace the power unit.
- 07Check the line supply phases.
- 08Check the external braking resistor connection.
Also in the manual
- Reaction OFF2: the motor coasts down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
03 / Clearing it
How to clear F30001
- Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
- Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
- If the cause is not removed, the fault can come back after five seconds with no button pressed.
- Alarms acknowledge themselves.
Clear it once. If F30001 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How overcurrent faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
- 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
- 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
- 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
- 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.
05 / Repair
When F30001 means a repair
If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.
If F30001 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Overcurrent: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F1 Overcurrent · A501 Current limit |
| Siemens SINAMICS G120 | F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active |
| Siemens MICROMASTER 440 | F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value |
| Allen-Bradley PowerFlex 525 | F012 HW OverCurrent · F063 SW OverCurrent |
| ABB ACS355 | F0001 OVERCURRENT · A2001 OVERCURRENT |
| Delta VFD-E | oc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed |
| Delta C2000 | ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop |
| Delta ASDA-B2 | AL001 Over current |
| Hitachi WJ200 | E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions |
| Schneider Electric Altivar ATV320 | OCF Overcurrent error |
| INVT Goodrive20 (GD20) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Yaskawa V1000 | oC Overcurrent · HCA Current Alarm |
| Yaskawa A1000 | oC Overcurrent · HCA Current Alarm |
| Yaskawa GA500 | oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm |
| Siemens MICROMASTER 420 | F0001 Overcurrent · A0501 Current limit value |
| Siemens MICROMASTER 430 | F0001 Overcurrent · A0501 Current limit value |
| Siemens SINAMICS G110 | F0001 Overcurrent · A0501 Current limit |
| INVT Goodrive200A (GD200A) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Mitsubishi Electric FR-D700 | E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent) |
| Danfoss VLT Micro Drive FC 51 | Alarm 13 Over current · Warning 59 Current limit |
07 / More codes
Other SINAMICS V90 codes
Source
Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007