MachineryFix

Siemens AC drive (VFD) · fault code

SINAMICS V20 F1: Overcurrent

F1 on the Siemens SINAMICS V20 is the “Overcurrent” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.

The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.

Code
F1
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V20
Kind of fault
Overcurrent

01 / Causes

What causes F1

  • The motor power set in P0307 does not match the inverter's power (r0206).
  • A short circuit in the motor leads.
  • An earth fault.

02 / Checks

What to check for F1

In the order Siemens gives them.

  1. 01Make sure the motor power in P0307 matches the inverter power in r0206.
  2. 02Make sure the motor cable is within the allowed length.
  3. 03Check the motor cable and motor for short circuits and earth faults.
  4. 04Check the motor parameters match the motor actually fitted, and that the stator resistance in P0350 is correct.
  5. 05Make sure the motor is not obstructed or overloaded.
  6. 06Increase the ramp-up time (P1120) and reduce the starting boost (P1312).

Also in the manual

  • Fault value r0949 = 0 or 22 means the hardware reported the overcurrent; r0949 = 1 means the software did.

03 / Clearing it

How to clear F1

  • Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
  • Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
  • Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.

Clear it once. If F1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How overcurrent faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
  2. 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
  3. 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
  4. 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
  5. 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.

05 / Repair

When F1 means a repair

If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.

If F1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Overcurrent: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active
Siemens SINAMICS V90F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U
Siemens MICROMASTER 440F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value
Allen-Bradley PowerFlex 525F012 HW OverCurrent · F063 SW OverCurrent
ABB ACS355F0001 OVERCURRENT · A2001 OVERCURRENT
Delta VFD-Eoc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed
Delta C2000ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop
Delta ASDA-B2AL001 Over current
Hitachi WJ200E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions
Schneider Electric Altivar ATV320OCF Overcurrent error
INVT Goodrive20 (GD20)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Yaskawa V1000oC Overcurrent · HCA Current Alarm
Yaskawa A1000oC Overcurrent · HCA Current Alarm
Yaskawa GA500oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm
Siemens MICROMASTER 420F0001 Overcurrent · A0501 Current limit value
Siemens MICROMASTER 430F0001 Overcurrent · A0501 Current limit value
Siemens SINAMICS G110F0001 Overcurrent · A0501 Current limit
INVT Goodrive200A (GD200A)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Mitsubishi Electric FR-D700E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent)
Danfoss VLT Micro Drive FC 51Alarm 13 Over current · Warning 59 Current limit

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F1 won't clear? Get a technician who knows the SINAMICS V20.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.