MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 oC: Overcurrent

oC on the Yaskawa GA500 is the “Overcurrent” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.

Code
oC
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Overcurrent

01 / Causes

What causes oC

  • The load is too heavy, the acceleration time too short, the motor too large or specialised for the drive, or a contactor was switched on the output.
  • Motor insulation damaged by overheating, the motor cable shorting to ground, or a short or ground fault that damaged the output transistor.
  • V/f pattern or torque compensation gain wrong, overexcitation gain too high, a run command while the motor coasted, the PM motor code wrong, the control method wrong for the motor, the motor cable too long, or electrical interference.

02 / Checks

What to check for oC

In the order Yaskawa gives them.

  1. 01Measure the motor current; if it is above the drive's rating, reduce the load or fit a larger drive.
  2. 02Measure the motor insulation resistance, and replace the motor if it conducts or the insulation is unserviceable.
  3. 03Examine the motor cable for damage and repair short circuits; measure the resistance between the motor cable and the ground terminal, and replace the cable if it conducts.
  4. 04Check for a short circuit between terminal B1 and U/T1, V/T2, W/T3, and between the - terminal and U/T1, V/T2, W/T3; if there is one, contact Yaskawa.
  5. 05Lengthen the acceleration times (C1-01, C1-03, C1-05, C1-07) and S-curve times (C2-01 to C2-04).
  6. 06Check the drive's rated current is above the motor's.
  7. 07Do not switch the output contactor while the drive is outputting voltage.
  8. 08Adjust the V/f pattern (E1-04 to E1-10) and lower C4-01 (torque compensation gain).
  9. 09Lower n3-13 (overexcitation braking gain) and n3-21 (HSB current suppression level).
  10. 10Give the run command only after the motor has fully stopped, or set b3-01 = 1 (Speed Search at Start) or H1-xx = 61 or 62 (Speed Search from Fmax or Fref).
  11. 11Set E5-01 (PM Motor Code Selection) for the motor; for special motors, set the E5 parameters from the motor test report.
  12. 12Set A1-02 (control method) correctly, and for long motor cables lower C6-02 or set C6-02 = B.
  13. 13If the trip happens at start or below 10% speed with n8-57 = 1 (HFI Overlap) in a PM control method, the high frequency injection gain is too high: set the E5 parameters correctly or do Rotational Auto-Tuning, and lower n8-41 in steps of 0.5 (keep n8-41 above 0.0 for IPM motors).
  14. 14With A1-02 = 8 (EZ Vector Control) and an induction motor (E9-01 = 0), speed search may not complete at start: set b3-24 = 2 (Current Detection Speed Search).
  15. 15With an IE3 premium efficiency motor, double the defaults of b3-03, L2-03 and L2-04.

03 / Clearing it

How to clear oC

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If oC comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How overcurrent faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
  2. 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
  3. 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
  4. 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
  5. 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.

05 / Repair

When oC means a repair

If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.

If oC keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Overcurrent: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F1 Overcurrent · A501 Current limit
Siemens SINAMICS G120F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active
Siemens SINAMICS V90F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U
Siemens MICROMASTER 440F0001 Overcurrent · F0022 Hardware monitoring active · A0501 Current limit value
Allen-Bradley PowerFlex 525F012 HW OverCurrent · F063 SW OverCurrent
ABB ACS355F0001 OVERCURRENT · A2001 OVERCURRENT
Delta VFD-Eoc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed
Delta C2000ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop
Delta ASDA-B2AL001 Over current
Hitachi WJ200E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions
Schneider Electric Altivar ATV320OCF Overcurrent error
INVT Goodrive20 (GD20)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Yaskawa V1000oC Overcurrent · HCA Current Alarm
Yaskawa A1000oC Overcurrent · HCA Current Alarm
Siemens MICROMASTER 420F0001 Overcurrent · A0501 Current limit value
Siemens MICROMASTER 430F0001 Overcurrent · A0501 Current limit value
Siemens SINAMICS G110F0001 Overcurrent · A0501 Current limit
INVT Goodrive200A (GD200A)OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running
Mitsubishi Electric FR-D700E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent)
Danfoss VLT Micro Drive FC 51Alarm 13 Over current · Warning 59 Current limit

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oC won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.